Please make sure that the size and position of the
printed label correspond to the module. After cut‐
ting, the label can be inserted into the mask
window from top.
4.2 ToolKit Configuration easYlite-200
4.2.1 Parameter Configuration
Fig. 13 shows the ToolKit configuration window, where easy‐
Lite-200's parameters can be set:
Fig. 13: easYlite-200 parameter configuration
In the first drop-down menu ("Module"), either of the two easY‐
lite-200 devices is selected.
In "Baud rate", the rate of data transmission for RS-485 is set.
The third drop-down list allows to select the number of stop bits in
the transmitted data (one or two) for RS-485, the fourth - the CAN
bus baud rate.
Finally, in the fifth menu the bit is set for the relay output. If "Horn "
is chosen, the relay will be energized upon incoming alarm set in
the easYgen device. If "Com Fail" is selected, the output is closed
when communication failure is detected. The third option enables
to energize the relay when either of these takes place.
If the relay is configured to "Horn" or "Horn or Com
fail“, the relay will be energized upon any occurring
genset alarm, regardless of whether the alarm is
assigned to an easYlite-200 LED or not. It is rec‐
ommended to also assign the configurable alarm
message "Horn" to one of the easYlite-200 LEDs
(see Fig. 10), in order to prevent an enabling of the
horn without an alarm indication at the easY‐
lite-200.
Configuration
ToolKit Configuration easYli... > Parameter Configuration
37903A
easYgen Expansion Module | LED Lamp Expansion Module
24