No. Function
Cable
Size
Description
8
Connect the CAN bus port to CAN port of easYgen
series controllers. It is recommended to use a shield
with the impedance of 120 Ω, with one end
grounded. The terminal provides resistance of 120 Ω;
if needed, short-circuit terminals 6, 7.
CAN (H)
9
RELAY
2.5mm
2
Relay output:
7 Aac 250 Vac, resistive, GP, potential-free contacts
7 Adc 28 Vdc, resistive, GP, potential-free contacts
10
2.5mm
2
Common pin of relay
Table 2: easYlite-200 terminals
3.3 Wiring diagram
Battery Voltage Input
This device can be used with batteries providing
the operating voltage range from 8 to 35 V
DC
.
The negative pole of the battery must be
grounded. The wire between the power supply ter‐
minals and the battery must have a cross section
above 2.5 mm
2
.
Fig. 5: Wiring diagram easYlite-200
3.4 Power Supply
Battery Voltage Input
This device can be used with batteries providing
the operating voltage range from 8 to 35 V
DC
.
The negative pole of the battery must be
grounded. The wire between the power supply ter‐
minals and the battery must have a cross section
above 2.5 mm
2
.
General Notes
General notes
Installation
Power Supply