Manual 26824
CPC-II Unit Replacement Procedure
Woodward
39
Verify CPC-II unit shutdown condition based on (See PC Service Tool tab
“Overview”):
Point 1. – Unit has established connection with Service Tool
Point 2. – Shutdown condition is annunciated by red LED indicator.
Point 3. – Setpoint is equal or below 4 mA
Point 4. – Setpoint Fault condition is annunciated be red LED indicator.
Figure 6-6. Basic parameters verification.
Operate the CPC-II unit in Manual Mode by setting the setpoint to the minimum
control pressure (See PC Service Tool tab “Performance Trend and Manual
Operation”).
-
Parameter: Manual Control Settings
o
Mode:
Enabled