Manual 26824
CPC-II Unit Replacement Procedure
Woodward
33
Place the CPC-II unit on CPC-DX manifold and simultaneously run wire bundle
through Electrical Terminal Box entry fitting.
Figure 5-2. CPC-II wires inside Electrical Terminal Box
Use a long hex wrench 2.5 – 2.7 inch (63-69 mm) to tighten 4 (four) bolts (CW
direction). Access to the bolt from the bottom of the CPC-DX manifold. Hex
socket size 8 mm. Typical wrench shape is shown on picture below.
Figure 5-3. Long socket wrench
Screw size - metric SOC HD Cap, M10 x 1.50, 3.15 inch long (80 mm) – 4
pieces, torque to 20-25 lbf-ft (27 – 34 Nm).