background image

Number

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

Description

Main unit

133mm 

×

 58mm

×

 35mm

100mm 

×

 62mm

×

 36mm

/

/

/

/

/

/
/

/

Detachable handpiece

Adapter of power supply

Foot switch 

Scaling tip

Water line 

Torque wrench

Handpiece decorative ring

Waterproof 

"

o

"

 ring

Packing list 

Instruction manual

Warranty card 

Qualified certificate

Endochuck

Endo wrench

Type

2

The  Woodpecker  scaling tips and their accessories are not listed in 
this instruction manual  completely.  The detail  can be found in the 
instruction for tips and packing list  attached to the machine.

18mm

×

117mm

6mm

×

 

 

4mm

32mm

×

39mm

17mm

×

 

 

15.4mm

×

2mm

3.2mm

×

1.1mm

1.2 Components

1.2.1 The following parts should be included in a complete

"

Woodpecker

"

 

 UDS-A  ultrasonic piezo scaler

1.2.2

 

Product performance and structure

a

Ultrasonic piezo scaler is composed of electrocircuit, waterway and 

ultrasonic transducer.

1.2.3

 

Scope of application

a

Ultrasonic  piezo  scaler  UDS-A  is used  for  the  dental  calculus 

elimination and root canal treatment

.

Summary of Contents for 824/00

Page 1: ...Guilin Woodpecker Medical Instrument Co Ltd Website www glwoodpecker com ULTRASONIC PIEZO SCALER INSTRUCTION MANUAL Please read this manual before operating UDS A ...

Page 2: ...rilization of scaling tips endo wrench and endochuck 3 3 Sterilization of torque wrench 3 4 Cleaning of tips endochuck torque wrench and endo wrench 3 5 Trouble analysis solutions and notes 4 Precaution 4 1 Notice when using equipment 4 2 Contraindication 4 3 Storage and maintenance 4 4 Transportation 4 5 Working condition 5 After service 6 Symbol instruction 7 Environmental Protection 1 1 1 3 3 7...

Page 3: ...scaler has scaling perio and endo functions It contains the following features 1 Automatic frequency tracking ensures that the machine always works on the best frequency and more steadily 2 The handpiece is detachable and can be autoclaved under the high 0 temperature of 135 C and the pressure of 0 22MPa 3 Digitally controlled easy operation and more efficient for scaling These features make UDS A...

Page 4: ...ies are not listed in this instruction manual completely The detail can be found in the instruction for tips and packing list attached to the machine 18mm 117mm 6mm 4mm 32mm 39mm 17mm 15 4mm 2mm 3 2mm 1 1mm 1 2 Components 1 2 1 The following parts should be included in a complete Woodpecker UDS A ultrasonic piezo scaler 1 2 2 Product performance and structure a Ultrasonic piezo scaler is composed ...

Page 5: ...f main unit 0 65kg k Weight of power source 0 3kg l main unit volume 184mm 134mm 80mm m Operating mode Continuous operation n Type of protection against electric shock Class II o Degree of protection against electric shock Type BF equipment p Degree of protection against harmful ingress of water Ordinary equipment IPX0 Protection degree against water used on the switch IPX1 q Degree of safety of a...

Page 6: ... connection a The components of the equipment 4 Picture 1 Power switch Socket for foot switch Socket for power supply Water entrance Water control knob Scaling indicator Endo indicator Perio indicator Options switch Decreasing power switch Increasing power switch Power indicator ...

Page 7: ...it c Sketch map for connection of wate supply system 5 Plug of foot switch Foot s switch ocket Foot switch Plug of foot switch Power supply Socket for power supply Power cord plug Power cord plug Input voltage 100V 240V Cap of one way connector Connect pure water Water line Water entrance ...

Page 8: ...cable Handpiece Nipple Seal Shaft Handpiece Picture 4 Autoclavable symbol Brand CE mark The connector of cable Handpiece Cable e Sketch map for how to install tip and endochuck with wrench Picture 5 I O Torque wrench Tip Handpiece Screw on Screw on Screw on Endochuck Endo wrench File ...

Page 9: ...ing indicator and the first five lights of power regulator shine h Select a suitable scaling tip as you need screw it on the handpiece tightly by the torque wrench picture 5 i The normal frequency is extremely high Under the normal working state of scaling tips a light touch and a certain to and fro motion will eliminate the tartar without heating Overexertion and long time lingering are forbidden...

Page 10: ...termly c Handpiece The main part of the whole handpiece can be autoclaved under the high temperature and pressure d The connector of the cable Connect the handpiece with the water source and power supply of the main unit Notice Keep dry when the detachable handpiece connect to the connector of the cable 2 1 3 Torque wrench use instruction showed in picture 5 a The torque wrench s structure is desi...

Page 11: ...he screw cap on the endochuck Put the ultrasonic file into the hole in the front of endochuck Screw down the screw cap with endo wrench to tight up the ultrasonic file Press option key turn to endo function When ultrasonic scaler turns into endo function only the first lead light is on and the power is at 1st grade Put the ultrasonic file into the patient s root canal slowly step on the foot switc...

Page 12: ...damaged during the treatment or sterilization don t smear any protective oil on the surface of handpiece d There are two waterproof o rings at the end of handpiece Please lub ricate them with dental lube frequently as sterilization and repeated pull ing and inserting will reduce their using life Change a new one once it is damaged or worn excessively e The following sterilizing methods are forbidd...

Page 13: ...city Contact our dealers or us The fuse of transformer is broken Insert the foot switch to its socket tightly The foot switch is in loose contact Make the plug insert to the socket well The power line plug is in loose contact Dismantle the handpiece and send it to our company to repair Contact our dealers or us Something wrong with the cable Something wrong with the handpiece The connect plug betw...

Page 14: ...ture 5 The coupling between the ha ndpiece and the cable isn t dry Dry it by the hot air The tip is damaged note3 Change a new one There is water seeping from the coupling between the handpiece and the cable The u file doesn t vibrate There is noise coming from the endochuck The waterproof O ring is damaged The screw is loose The screw is loose Endochuck is damaged Change a new O ring Tighten it C...

Page 15: ...caution 4 1 Notice when using equipment 4 1 1 Keep the scaler clean before and after operation 4 1 2 The handpiece scaling tip torque wrench endo wrench and endochuck must be sterilized before each treatment 4 1 3 Don t screw or unscrew the handpiece scaling tip and endochuck when step on the foot switch 4 1 4 The scaling tip must be fastened and there must be fine spray or drip coming from the ti...

Page 16: ...2 2 The patients or doctors with heart pacemaker are forbidden to use this equipment 4 2 3 The heart disease patient pregnant woman and children should be cautious to use the equipment 4 3 Storage and maintenance 4 3 1 The equipment should be handled carefully and lightly Be sure that it is far from the vibration and installed or kept in a cool dry and ventilated place 4 3 2 Don t store the machin...

Page 17: ...97 Connection for the foot switch switch SOCKET Adjustment for the water flow Power switch H2O 30VDC power supply socket FDA marked product Trademark Use indoor only Class Ⅱequipment 4 5 Working condition 0 0 a Environment temperature 5 C 40 C b Relative humidity 80 c Atmosphere pressure 50kPa 106kPa 6 Symbol instruction 5 After service Temperature limitation Humidity limitation Atmospheric pressu...

Page 18: ...ngs the instruction manual and the content of the original packing list at any time without notice If there are some differences between blueprint and real equipment take the real equipment as the norm 9 Declaration of conformity 9 1 EN 60601 1 1990 A1 1993 A2 1995 A13 1996 EN 60601 1 2 2001 EN 60601 1 4 2001 EN 61205 1994 EN ISO 22374 2005 EN ISO 14971 2000 A1 2003 EN 980 2003 ISO 9687 1993 EN 10...

Page 19: ...e ESD lEC 61000 4 2 6 kV contact 8 kV air 6 kV contact 8 kV air Floors should be wood concrete or ceramic tile If floors are covered with synthetic material the relative humidity should be at least 30 Electrical fast transient burst IEC 61000 4 4 2kV for power supply lines 1 kV for Input output lines 2kV for power supply lines Mains power quality should be that of a typical commercial or hospital ...

Page 20: ... a b Immunity test IEC 60601 test level Compliance level Electromagnetic environment guidance Portable and mobile RF communications equipment should be used no closer to any part of the model UDS A including cables than the recommended separation distance calculated from the equation applicable to the frequency of the transmitter Recommended separation distance 3V 3V 3 V m d 2 3 P1 2 800 MHz to 2 ...

Page 21: ... use in an electromagnetic environment in which radiated RF disturbances are controlled The customer or the user of the model UDS A can help prevent electromagnetic interference by maintaining a minimum distance between portable and mobile RF communications equipment transmitters and the model UDS A as recommended below according to the maximum output power of the communications equipment Separati...

Page 22: ...China Tel 86 773 5855350 English service for 24 hours 86 773 5831172 Fax 86 773 5822450 E mail woodpecker gx163 net Website www glwoodpecker com Guilin Woodpecker Medical Instrument Co Ltd Copyright WOODPECKER Edition Mar 22 2008 02E c ...

Reviews: