background image

SYMPTOM 

POSSIBLE CAUSE 

ACTION

1. Spark ignitor will not

light pilot after repeated
triggering of piezo.

2. Pilot will not stay lit

after carefully following
lighting instructions.

A.  Wire disconnected.

B.  Defective ignitor.

C.  No gas or low gas pressure.

D.  No Propane/LPG in tank

A.  Defective thermocouple

B.  Defective valve

A.  Open door and check to make sure wire is connected to ignitor.
B.   Check for spark at electrode and pilot. If no spark and electrode 

wire is properly connected, replace pilot assembly. 

C.  Check remote/manual shut off valve from fireplace. Low pressure 

can be caused by bent lines, restricted lines, low pressure line pres-
sure. Consult with plumber or gas supplier. 

D.  Check Propane/LPG tank. Refill tank.

A.  Check that thermocouple flame impinges on thermocouple. Clean 

and/or adjust pilot for maximum flame impingement. Ensure that 
the thermocouple connection at the gas valve is fully inserted and 
tight. 

Disconnect the thermocouple from the valve, place one millivolt 

lead wire on the tip of the thermocouple and the other meter lead 
wire on the thermocouple copper lead. Start the pilot and hold the 
valve knob in. If the millivolt reading is less than 15 mV, replace 
pilot assembly. 

B.   If thermocouple is producing more than 15 mV, replace 

faulty valve.

 

TROUBLESHOOTING 

3. Pilot burning, valve

knob turned to “ON”,
switch is turned to

burner will not ignite.

4. Frequent pilot outage

problem.

5. The pilot and main

burner extinguish while
in operation

A.  Defective switch, wall switch, 

remote control or wire

B.  Pilot flame too small

C.  Defective or malfunctioning 

thermopile

D.  Defective valve

A.  Pilot flame may be too high or 

too low, causing pilot safety to 
drop out 

A.  Inner vent pipe leaking exhaust 

gases back into system 

B.  Horizontal vent improperly 

pitched 

C.  Improper vent cap installation

A.  Check switch and wire for proper connection. Place jumper wires 

across terminals of switch. If burner comes on, replace defective 
switch.If the switch is OK, repeat the same procedure on remote 
control If burner comes on, replace remote control. 

Place jumper wire across wire at gas valves (terminals marked TH 

and TP/TH). If burner comes on, wires are faulty or connections 
are bad. Replace wire.

B.   If pilot flame is not close enough to the thermopile, adjust 

pilot flame.

C.   Check thermopile wire connections to make sure all are tight and 

that the thermopile is fully inserted into pilot assembly. Check 
thermopile with a millivolt meter. Connect leads to TP and TP/
TH terminals on the control valve. If meter reading is below 325 
mV, replace pilot assembly.

D.   Turn valve knob to “O

N

” and switch to “ON.” Take a reading at 

the thermopile leads (TP & TP/TH) on the valve. If the meter 
reads greater than 175 mV and the burner does not light, replace 
defective valve.

A.  Clean and adjust the pilot flame for maximum flame impingement 

on thermocouple.

A.  Check for flue product leak. Replace defective pipe section.

B.  Check horizontal-venting piping is running upward 1/4" per foot. 

Do not run the pipe level or downward. 

C.   Check for proper installation and freedom from debris or blockage.

 

 

6

. Flame burn blue and

lifts off burner (ghost-
ing)

 

A.  Insufficient oxygen being supplied 

 

 

A.  Ensure that the vent cap is installed properly and free of debris. Ensure that 

the vent system joints are tight and have no leaks. Ensure that no debris has 
been blocking the inner air intake at the bottom back of the combustion 
chamber. Ensure that the glass is properly secure and latch.

43

B.   Check that inlet pressure meets requirements.   

“ON”, but

Summary of Contents for MONTEREY-(N

Page 1: ...SION HAZARD Failure to follow safety warnings exactly could result in serious injury death or property damage Do not touch any electrical switch do not use any phone in your building Do not try to lig...

Page 2: ...Type 25 Installing Gas Piping to Fireplace Burner System Location 25 Checking Gas Pressure 27 Electrical Installation 28 Electrical Wiring 28 Wall Switch 28 Glass Removal 29 Final Installation 30 Medi...

Page 3: ...d and sealed If this unit is not properly installed by a qualified service person with glass panel properly seated and sealed combustion leakage can occur CARBON MONOXIDE POISONING Early signs of carb...

Page 4: ...ace to give off some odor the first time it is burned This is due to the manufacturing process Please ensure that your room is well ventilated during burn off open all windows It is recommended that y...

Page 5: ...Remote Control Receiver optional 4 Blower Speed Control 5 Blower 6 Duplex Outlet for Blower located against lower right outside wall 6 Figure 1 Fireplace controls TESTED TO ANSI Z21 88 2014 CSA 2 33 2...

Page 6: ...damage and immediately inform the distributor if any damage is found Do not install any unit with damaged incomplete or substitute parts Check your packing list to verify that all listed parts have be...

Page 7: ...rial over the facing are 60 x 34 1 2 see Figure 2 3 The inner opening in covering material must be minimum 49 1 4 wide 14 1 4 tall and centered over the fireplace opening to allow for or glass door re...

Page 8: ...RMATION Figure 3 Fireplace Dimensions Right side view Front view Top view Flue collar Electric access both sides Gas line access both sides 28 34 25 23 25 48 75 13 75 59 25 34 25 28 7 125 7 125 8 5 22...

Page 9: ...t the front opening of the fireplace Do not install in the vicinity where gasoline or other flammable liquids may be stored Vent pipe routing See Venting section found in this manual for allowable ven...

Page 10: ...ecure fireplace to the floor Use four 4 screws to attach fireplace to framing The side brackets are adjustable from 1 2 to 5 8 to accommodate different thickness of material SECURING FIREPLACE TO FLOO...

Page 11: ...l flooring the appliance shall be installed on a metal wood or noncombustible material panel extending full width and depth of the appliance WARNING The fireplace face may be covered with any non comb...

Page 12: ...NFORMATION VENT INSTALLATION Never obstruct or modify the air inlet or outlet This may create a fire hazard WARNING Read all instructions completely and thoroughly before attempting installation Failu...

Page 13: ...be attached to a chimney serving a separate solid fuel burning appliance Each gas appliance must use a separate vent system Do not use common vent systems WARNING Horizontal sections of this vent sys...

Page 14: ...s firestops are required at each floor level If an offset is needed in the attic additional pipe and elbows will be required You may use a chase with a vent termination with exposed pipe on the exteri...

Page 15: ...n air inlet to any other appliance 12 305mm minimum K Clearance to a mechanical air supply inlet 6 1829mm minimum L Clearance above a paved sidewalk or paved driveway located on public property 7 2133...

Page 16: ...cal line to the bottom of the graph 3 Select the indicated dimension and position the fireplace in accordance with same Example If the vertical dimension from the floor of the fireplace is 11 3 4m the...

Page 17: ...ired combination of pipe and elbows to the appliance adaptor with pipe seams oriented towards the wall or floor Twist lock Procedure The female ends of the pipes and fittings have three locking lugs i...

Page 18: ...re 15 5 Slide the wall thimble over the vent pipe before connecting the horizontal run to the vent cap See Figure 16 6 Carefully move the fireplace with vent assembly attached toward the wall and inse...

Page 19: ...dations less than 20 below siding outcrop the vent pipe must flush up with the sid ing It is best to locate the fireplace in such a way that minimizes the number of offsets and horizontal vent length...

Page 20: ...lbows permitted per side wall installation is two 2 These elbows can be installed in either the vertical or horizontal run For each 45 elbow installed in the horizontal run the length of the horizonta...

Page 21: ...leaving a clearance of approximately 4 below snorkel See Figure 21 3 Install vent system 4 Ensure a watertight seal is made around the vent pipe coming through the wall 5 Apply high temperature sealan...

Page 22: ...at you first determine the roof pitch and use the appropriate starter kit The maximum angular variation allowed in the system is 270 See Figure 26 The minimum height of the vent above the high est poi...

Page 23: ...x101 2 267mm x 267mm inside dimensions as shown in Figure 12 page 17 using framing lumber the same size as the ceiling joist If the area above the ceiling is an insulated ceiling or a room nail fires...

Page 24: ...eiling Support Box Installation Figure 31 Installed Cathedral Ceiling Support Box CATHEDRAL CEILING INSTALLATION IMPORTANT Review all information on previous page before planning this installation Cat...

Page 25: ...l regulator will reduce incoming gas pressure You must reduce incoming gas pressure to between 11 and 13 inches of water If you do not reduce incoming gas pressure burner system regulator damage could...

Page 26: ...raps moisture and contaminants This keeps them from going into the burner system gas controls If sediment trap drip leg is not installed or is installed wrong burner system may not run properly Figure...

Page 27: ...aking pressure reading be sure and turn captured screw clockwise firmly to reseal Do not over torque Check test points for gas leaks Figure 34 Gas Pressure Check at Gas Valve Pressure Test IN Pressure...

Page 28: ...without any electrical supply Electricity is only needed to operate blower NOTE If installed in mobile home fireplace must be bolted securely to floor Electrical connections should only be performed...

Page 29: ...lifting up and moving to the center Figure 36 Removing Glass Frame and tilting out the upper right corner Front air panel Right side panel 4 Remove upper door bracket NOTE Avoid contacting the glass t...

Page 30: ...37 on the support brackets as shown on figure 38 Figure 37 One piece media tray Figure 38 Placing media tray Figure 39 Filling the tray with media 2 Fill the tray with media supplied Do not place medi...

Page 31: ...LOG SET 31...

Page 32: ...Figure 41 Log set placement LOG SETT contunue 32...

Page 33: ...the screen in place Using the nuts provided attach the screen firmly 33 WARNING A barrier safety screen designed to reduce the risk of burns from the hot viewing glass is provided with this appliance...

Page 34: ...the face and slide downward Make sure the side panel is secured properly Repeat Steps 5 and 6 for the Left Side Panel STEP 7 Angle the Air Front Panel beneath the bottom of the screen Support the Air...

Page 35: ...air may result in a fire or explosion D Do not use this appliance if any part of it has been under water Immediately call a qualified service technician to inspect the appliance and to replace any par...

Page 36: ...gas leaks in each of the following locations Pipe from the gas supply line connection to the gas valve Burner connections Field made joints gas shutoff valve Pilot Factory made joints Each joint or c...

Page 37: ...alve knob Make sure the switch is in the ON position to light the main burner LIGHTING THE BURNER Depress and turn the knob counterclockwise to the ON position See Figure 42 It will take less than fou...

Page 38: ...ore See Figure 47 Figure 46 Burner Flame Appearance CLEANING AND MAINTENANCE BURNER PILOT AND CONTROL COMPARTMENT Keep the control compartment and burner areas clean by vacuuming or brushing at least...

Page 39: ...LOG SET Replace logs or add media as required following unstallation instructions in the Final Installation section of this manual BLOWER FAN ASSEMBLY The fan assembly has an automatic temperature co...

Page 40: ...9 Pipe Length 58DVA 09 3 4 12 Pipe Length 58DVA 12 3 4 24 Pipe Length 58DVA 24 3 4 36 Pipe Length 58DVA 36 3 4 48 Pipe Length 58DVA 48 4 4 8 1 2 Pipe Extension 58DVA 08A 4 4 16 Pipe Extension 58DVA 1...

Page 41: ...ILLUSTRATED PARTS LISTS BURNER COMPARTMENT 9 3 10 11 12 FIREBOX ACCESS AND MEDIA COMPONENTS CONTROL COMPARTMENT 13 1 3 4 2 5 6 7 6 6 8 14 22 41 18 21 20 19 23 22...

Page 42: ...ORIFICE 1 10 W400071 W400071 BURNER 1 11 C100003 C100004 PILOT ASSEMBLY 1 12 D100019 D100019 PILOT BRACKET 1 13 F200100 F200100 3 8 NPT X 5 16 COMPRESSION CONNECTOR 1 14 F200064 F200064 3 8 NPT X 3 8...

Page 43: ...safety to drop out A Inner vent pipe leaking exhaust gases back into system B Horizontal vent improperly pitched C Improper vent cap installation A Check switch and wire for proper connection Place ju...

Page 44: ...127 6...

Page 45: ...127 6...

Page 46: ...127 6...

Page 47: ...0 Elbows Quantity 45 Elbows ALTITUDE Feet Above Sea Level Was Stove Derated Yes No If Yes To What Orifice Size Unusual Structure Near Vent Inside Corner Trees Shrubs Other Termination Please Describe...

Page 48: ...stallation or transportation of defective parts on the appliance or 3 incidental or consequential damage All service work must be performed by an authorized service representative This warranty is exp...

Reviews: