background image

16

L100001

 

17

10

��

67

���

10

��

67

���

5.25

134

���

8

216

���

Figure 12 - Vent Opening Requirements 

Note: Horizontal runs of vent must 

be  supported  every  three  feet 

(914mm). Use wall straps for this 

purpose. 

Figure 13 - Rigid Vent Pipe Connections

Female Locking Lugs 

Male Slots

REAR WALL VENT INSTALLATION 

When  installed  as  a  rear  vent  unit  this  appliance  may  be  vented  directly  to  a  termination  located  on  the  rear  wall  behind 

the appliance with 1' of vertical rise minimum.

  The maximum horizontal distance between the rear of the appliance and the outside of termination is 20" (508 m). 

See 

Figure 11.

VENTING INSTALLATION  

1. Locate and cut the vent opening in the wall. For com-

bustible walls first frame in opening. 

See Figure 11.

Combustible  Walls:

 

Cut  a 

10

1

2

"H  x 

10

1

2

"  W

(

267mm x 267mm

)  hole  through  the  exterior  wall

and frame as shown. 

See Figure 12.

Noncombustible Walls:

 

Hole opening should be

8

1

2

" (

216

mm) in diameter.

2. Rigid vent pipes and fittings have special twist-lock

connections. Assemble the desired combination of
pipe and elbows to the appliance adaptor with pipe
seams oriented towards the wall or floor.

Twist-lock Procedure:

 The female ends of the pipes

and fittings have three locking lugs (indentations).
These lugs will slide straight into matching slots on
the male end of adjacent pipes and fittings. Push
the  pipe  sections  together  and  twist  one  section
clockwise approximately one-quarter turn until the
sections are fully locked. 

See Figure 13.

3. Attach vent pipe assembly to the fireplace. Set fire-

place in front of its permanent location to insure
minimum clearances. Mark the wall for a

 10

1

2

"H

x

  10

1

2

"W 

(

241mm x 241 mm

)

 

square

  hole  (for

noncombustible material such as masonry block or
concrete, a 

8

1

/

2

" [

216

mm] diameter hole is accept-

able). 

See Figure 11. 

The center of the hole should 

line up with the center line of the horizontal rigid
vent pipe end. Be sure to allow for minimum rise. Cut a 

10-

1/2"x10-1/2" (267mm X 267mm)

 

square 

hole through combustible

exterior wall (

8

1

/

2

" [

216

mm] diameter hole if noncombustible). Frame as necessary. Allow 

1

/

4

" minimum rise per foot. 

See

Figure 12.

Figure 11 - Rear Vent Application,

Maximum Horizontal Distance 

6

6

Maximum

      20"

Summary of Contents for MONTEREY-(N

Page 1: ...SION HAZARD Failure to follow safety warnings exactly could result in serious injury death or property damage Do not touch any electrical switch do not use any phone in your building Do not try to lig...

Page 2: ...Type 25 Installing Gas Piping to Fireplace Burner System Location 25 Checking Gas Pressure 27 Electrical Installation 28 Electrical Wiring 28 Wall Switch 28 Glass Removal 29 Final Installation 30 Medi...

Page 3: ...d and sealed If this unit is not properly installed by a qualified service person with glass panel properly seated and sealed combustion leakage can occur CARBON MONOXIDE POISONING Early signs of carb...

Page 4: ...ace to give off some odor the first time it is burned This is due to the manufacturing process Please ensure that your room is well ventilated during burn off open all windows It is recommended that y...

Page 5: ...Remote Control Receiver optional 4 Blower Speed Control 5 Blower 6 Duplex Outlet for Blower located against lower right outside wall 6 Figure 1 Fireplace controls TESTED TO ANSI Z21 88 2014 CSA 2 33 2...

Page 6: ...damage and immediately inform the distributor if any damage is found Do not install any unit with damaged incomplete or substitute parts Check your packing list to verify that all listed parts have be...

Page 7: ...rial over the facing are 60 x 34 1 2 see Figure 2 3 The inner opening in covering material must be minimum 49 1 4 wide 14 1 4 tall and centered over the fireplace opening to allow for or glass door re...

Page 8: ...RMATION Figure 3 Fireplace Dimensions Right side view Front view Top view Flue collar Electric access both sides Gas line access both sides 28 34 25 23 25 48 75 13 75 59 25 34 25 28 7 125 7 125 8 5 22...

Page 9: ...t the front opening of the fireplace Do not install in the vicinity where gasoline or other flammable liquids may be stored Vent pipe routing See Venting section found in this manual for allowable ven...

Page 10: ...ecure fireplace to the floor Use four 4 screws to attach fireplace to framing The side brackets are adjustable from 1 2 to 5 8 to accommodate different thickness of material SECURING FIREPLACE TO FLOO...

Page 11: ...l flooring the appliance shall be installed on a metal wood or noncombustible material panel extending full width and depth of the appliance WARNING The fireplace face may be covered with any non comb...

Page 12: ...NFORMATION VENT INSTALLATION Never obstruct or modify the air inlet or outlet This may create a fire hazard WARNING Read all instructions completely and thoroughly before attempting installation Failu...

Page 13: ...be attached to a chimney serving a separate solid fuel burning appliance Each gas appliance must use a separate vent system Do not use common vent systems WARNING Horizontal sections of this vent sys...

Page 14: ...s firestops are required at each floor level If an offset is needed in the attic additional pipe and elbows will be required You may use a chase with a vent termination with exposed pipe on the exteri...

Page 15: ...n air inlet to any other appliance 12 305mm minimum K Clearance to a mechanical air supply inlet 6 1829mm minimum L Clearance above a paved sidewalk or paved driveway located on public property 7 2133...

Page 16: ...cal line to the bottom of the graph 3 Select the indicated dimension and position the fireplace in accordance with same Example If the vertical dimension from the floor of the fireplace is 11 3 4m the...

Page 17: ...ired combination of pipe and elbows to the appliance adaptor with pipe seams oriented towards the wall or floor Twist lock Procedure The female ends of the pipes and fittings have three locking lugs i...

Page 18: ...re 15 5 Slide the wall thimble over the vent pipe before connecting the horizontal run to the vent cap See Figure 16 6 Carefully move the fireplace with vent assembly attached toward the wall and inse...

Page 19: ...dations less than 20 below siding outcrop the vent pipe must flush up with the sid ing It is best to locate the fireplace in such a way that minimizes the number of offsets and horizontal vent length...

Page 20: ...lbows permitted per side wall installation is two 2 These elbows can be installed in either the vertical or horizontal run For each 45 elbow installed in the horizontal run the length of the horizonta...

Page 21: ...leaving a clearance of approximately 4 below snorkel See Figure 21 3 Install vent system 4 Ensure a watertight seal is made around the vent pipe coming through the wall 5 Apply high temperature sealan...

Page 22: ...at you first determine the roof pitch and use the appropriate starter kit The maximum angular variation allowed in the system is 270 See Figure 26 The minimum height of the vent above the high est poi...

Page 23: ...x101 2 267mm x 267mm inside dimensions as shown in Figure 12 page 17 using framing lumber the same size as the ceiling joist If the area above the ceiling is an insulated ceiling or a room nail fires...

Page 24: ...eiling Support Box Installation Figure 31 Installed Cathedral Ceiling Support Box CATHEDRAL CEILING INSTALLATION IMPORTANT Review all information on previous page before planning this installation Cat...

Page 25: ...l regulator will reduce incoming gas pressure You must reduce incoming gas pressure to between 11 and 13 inches of water If you do not reduce incoming gas pressure burner system regulator damage could...

Page 26: ...raps moisture and contaminants This keeps them from going into the burner system gas controls If sediment trap drip leg is not installed or is installed wrong burner system may not run properly Figure...

Page 27: ...aking pressure reading be sure and turn captured screw clockwise firmly to reseal Do not over torque Check test points for gas leaks Figure 34 Gas Pressure Check at Gas Valve Pressure Test IN Pressure...

Page 28: ...without any electrical supply Electricity is only needed to operate blower NOTE If installed in mobile home fireplace must be bolted securely to floor Electrical connections should only be performed...

Page 29: ...lifting up and moving to the center Figure 36 Removing Glass Frame and tilting out the upper right corner Front air panel Right side panel 4 Remove upper door bracket NOTE Avoid contacting the glass t...

Page 30: ...37 on the support brackets as shown on figure 38 Figure 37 One piece media tray Figure 38 Placing media tray Figure 39 Filling the tray with media 2 Fill the tray with media supplied Do not place medi...

Page 31: ...LOG SET 31...

Page 32: ...Figure 41 Log set placement LOG SETT contunue 32...

Page 33: ...the screen in place Using the nuts provided attach the screen firmly 33 WARNING A barrier safety screen designed to reduce the risk of burns from the hot viewing glass is provided with this appliance...

Page 34: ...the face and slide downward Make sure the side panel is secured properly Repeat Steps 5 and 6 for the Left Side Panel STEP 7 Angle the Air Front Panel beneath the bottom of the screen Support the Air...

Page 35: ...air may result in a fire or explosion D Do not use this appliance if any part of it has been under water Immediately call a qualified service technician to inspect the appliance and to replace any par...

Page 36: ...gas leaks in each of the following locations Pipe from the gas supply line connection to the gas valve Burner connections Field made joints gas shutoff valve Pilot Factory made joints Each joint or c...

Page 37: ...alve knob Make sure the switch is in the ON position to light the main burner LIGHTING THE BURNER Depress and turn the knob counterclockwise to the ON position See Figure 42 It will take less than fou...

Page 38: ...ore See Figure 47 Figure 46 Burner Flame Appearance CLEANING AND MAINTENANCE BURNER PILOT AND CONTROL COMPARTMENT Keep the control compartment and burner areas clean by vacuuming or brushing at least...

Page 39: ...LOG SET Replace logs or add media as required following unstallation instructions in the Final Installation section of this manual BLOWER FAN ASSEMBLY The fan assembly has an automatic temperature co...

Page 40: ...9 Pipe Length 58DVA 09 3 4 12 Pipe Length 58DVA 12 3 4 24 Pipe Length 58DVA 24 3 4 36 Pipe Length 58DVA 36 3 4 48 Pipe Length 58DVA 48 4 4 8 1 2 Pipe Extension 58DVA 08A 4 4 16 Pipe Extension 58DVA 1...

Page 41: ...ILLUSTRATED PARTS LISTS BURNER COMPARTMENT 9 3 10 11 12 FIREBOX ACCESS AND MEDIA COMPONENTS CONTROL COMPARTMENT 13 1 3 4 2 5 6 7 6 6 8 14 22 41 18 21 20 19 23 22...

Page 42: ...ORIFICE 1 10 W400071 W400071 BURNER 1 11 C100003 C100004 PILOT ASSEMBLY 1 12 D100019 D100019 PILOT BRACKET 1 13 F200100 F200100 3 8 NPT X 5 16 COMPRESSION CONNECTOR 1 14 F200064 F200064 3 8 NPT X 3 8...

Page 43: ...safety to drop out A Inner vent pipe leaking exhaust gases back into system B Horizontal vent improperly pitched C Improper vent cap installation A Check switch and wire for proper connection Place ju...

Page 44: ...127 6...

Page 45: ...127 6...

Page 46: ...127 6...

Page 47: ...0 Elbows Quantity 45 Elbows ALTITUDE Feet Above Sea Level Was Stove Derated Yes No If Yes To What Orifice Size Unusual Structure Near Vent Inside Corner Trees Shrubs Other Termination Please Describe...

Page 48: ...stallation or transportation of defective parts on the appliance or 3 incidental or consequential damage All service work must be performed by an authorized service representative This warranty is exp...

Reviews: