Fault messages
If a fault is indicated by the signal ring of the control unit fl ashing red, a fault code is displayed
via the Wolf control accessory with eBUS capability that allows cause and effect to be allocated
using the following table.
This list of fault messages is designed to allow your heating contractor to trace the fault more
easily.
No. Fault
Cause
Effect / Remedy
1
TB excess temperature
The external temperatu-
re limiter has shut down
the system
Burner OFF, pump ON
Request a service
4
Burner fault
During the burner start
no fl ame was esta-
blished
Burner OFF, pump ON
Press the reset button at the com-
bustion controller or the control unit.
If the fault cannot be removed by
pressing the reset button several
times, request a service.
6
TW excess temperature The boiler water tem-
perature has exceeded
the limit for TW (e.g.
95 °C)
Burner OFF, pump ON
Request a service
8
Flue gas/ventilation air
damper does not move
Flue gas damper / ven-
tilation air damper or its
feedback faulty
Burner OFF, pump ON
12
Boiler sensor faulty
Boiler temperature
sensor or lead faulty
Burner OFF, pump ON
Request a service
14
Cylinder sensor faulty
Sensor for the DHW
temperature or for the
lead faulty
For heating mode:
No effect
Cylinder primary pump and heating
circuit pump cycle
alternately
1 h ON,
1 h OFF
Request a service
40
Fault maximum thermo-
stat, system pressure
limiter
The system pressure
switch or the maxi-
mum thermostat has
responded
Burner OFF, pump OFF
52
Max. cylinder heating
time exceeded
Cylinder heating takes
longer than permitted
Alternating cylinder heating and
central heating mode
15
Outside temperature
sensor faulty
Sensor for the outside
temperature faulty
(short circuit or break)
Effect as per outside temperature
below frost protection limit
Request a service
79
Fault multi-function sen-
sor (central sensor)
Central sensor faulty
(short circuit or break)
Control unit at set boiler water temp.
No effect on the boiler operation
Request a service
79
Fault multi-function sen-
sor (return sensor)
Sensor for the return
sensor faulty (short
circuit or break)
No effect on the boiler operation
bypass pump continues to run
Request a service
81
Fault EEPROM
Internal equipment fault Request a service
91
Fault eBUS parameter
One BUS address was
allocated more than
once
Request a service