Overview

Overview

3.1 

Unit description

The Link home and Link pro interface modules can be used to access WOLF 

control components remotely in order to view states and levels and change 

parameters. Over a secure internet connection. The WOLF Link home is 

designed to be installed in an appliance. The WOLF Link pro is designed for 

wall mounting.

Both interface modules can be integrated into an existing network either with 

a network cable (LAN) or wirelessly (WLAN).

They can be operated using the WOLF Smartset app (for iOS and Android), 

the WOLF portal on any platform (internet access required) or the Windows 

PC application WOLF Smartset.

Concurrent access

A system can only be accessed by one user at any time.

3.2 

Compatible appliances

WOLF 

Link 

home

WOLF 

Link pro

CGB-2, CGW-2, CGS-2 gas condensing boiler
TOB wall mounted oil condensing boiler
Gas condensing boilers MGK-2
BWL-1S split air source heat pump
COB oil condensing boiler
MGK gas condensing boiler
CGB, CGW, CGS, FGB gas condensing boilers
CGG-2, CGU-2 conventional gas boilers
R2, R3, R21 boiler control units
BWW-1, BWL-1, BWS-1 mono block heat pumps
MM, MM-2 mixer module
KM, KM-2 cascade module

  

in conjunction with a WOLF Link home compatible heating appliance, 

Full functional scope only with appliances running current software 

versions.

Note:

ISM8

WWW

ISM7i /

LINK HOME

ISM7e /

LINK PRO

DSL-ROUTER

WOLF 

PORTALSERVER

OPEN SOURCE COMMUNITY PROJECT

WWW.IOBROKER.NET

LAN/WLAN

128 BIT SECURITY 
ENCRYPTION

SYSTEM
INTERFACE
APP

HOSTED IN 

      GERMANY

LONWORKS

KM-2 cascade 

module

WOLF WRS-2 CONTROL SYSTEM

SM2-2 solar pump 

assembly

BM-2 

programming 

unit

Heat generator

Mechanical 

ventilation unit

Ventilation unit

Combined heat and power module

Smartset app/portal

Pump groups incl. 

MM-2 mixer  

BM-2 Solar

5

3066086_201803

Summary of Contents for Link home

Page 1: ...H 1380 D 84048 MAINBURG TEL 49 0 87 51 74 0 FAX 49 0 87 51 74 16 00 www WOLF eu Doc no 3066086_201803 Subject to modifications GB Installation and operating instructions WOLF Link home WOLF Link pro interface module WRS ...

Page 2: ... delivery 6 3 5 Overview WOLF Link home WOLF Link pro interface module 6 3 6 Function of the pushbutton 7 3 7 Meaning of the LEDs 7 3 8 Specification 7 4 Installation Electrical connection 8 4 1 Installation site requirements 8 4 2 WOLF Link home installation 8 4 3 WOLF Link pro installation 10 4 4 Decommissioning and disposal 11 4 4 1 Decommissioning 11 4 4 2 Disposal and recycling 11 5 Commissio...

Page 3: ...ed to as Link hereinafter 1 4 Symbols and warnings used Symbol for additional information X X Symbol for a necessary action Warnings in the text warn you of possible risks before the start of an instruction The warnings provide you with information on the possible severity of the risk using a pictogram and a keyword Pictogram Keyword Explanation Danger Risk to life or risk of serious injury Danger...

Page 4: ... have received instructions on how to use the appliance from this person 2 3 General safety instructions The Link interface module must be installed and commissioned by a qualified contractor Only qualified contractors may carry out the electrical installation X X Before working on the electrical installation disconnect the power supply from the appliance and all connected components X X Be aware ...

Page 5: ... condensing boiler TOB wall mounted oil condensing boiler Gas condensing boilers MGK 2 BWL 1S split air source heat pump COB oil condensing boiler MGK gas condensing boiler CGB CGW CGS FGB gas condensing boilers CGG 2 CGU 2 conventional gas boilers R2 R3 R21 boiler control units BWW 1 BWL 1 BWS 1 mono block heat pumps MM MM 2 mixer module KM KM 2 cascade module in conjunction with a WOLF Link home...

Page 6: ...s Connecting cable Network cable 3 x adhesive cable fasteners Additional label for attachment to housing 3 4 Wolf LINK pro standard delivery Check the standard delivery using the following list WOLF Link pro interface module Installation and operating instructions Network cable USB power supply unit and cable for power supply eBus connection cable 3 x strain relief Additional label for attachment ...

Page 7: ...On eBus and Modbus connection established and system detection completed Flashing System detection active WLAN Red Off WLAN disabled On WLAN connection established Flashing Connecting On for a long time briefly off Access point active Flashing quickly WPS active 3 8 Specification Designation Power supply WOLF Link home 24 VDC via PCB WOLF Link pro 5VDC via Micro USB and included power supply or 24...

Page 8: ...OFF the power supply to the appliances X X Secure the power supply against reconnection 4 1 Installation site requirements Only install the Link home interface module in the specific installation locations intended The WOLF Link pro may only be operated inside buildings and outside wet rooms 4 2 WOLF Link home installation CGB 2 CGW 2 CGS 2 and BWL 1S MGK 2 TOB X X Switch OFF the appliance and ass...

Page 9: ...X Clip the WOLF Link home in at the designated location X X Clip the WOLF Link home in at the designated location X X Clip the WOLF Link home in at the designated location HCM 2 X X In the case of network connection by network cable LAN plug this into the RJ45 socket on the WOLF Link home X X Switch on the appliance and associated components X X You can now use the WOLF Link home see instructions ...

Page 10: ...ea free of metallic objects e g cables and pipes X X Switch OFF the appliance and associated components X X Disconnect the power supply MCB or heating emergency stop switch X X Open the Wolf Link pro by undoing the screw and lifting up the cover on this side X X Carefully break out the required cable entries with a suitable tool e g needle nosed pliers 10 cm 10 cm LAN optional eBus WRS optional US...

Page 11: ...d screw it in place Use a shielded cable CAT5 minimum to connect the Modbus 4 4 Decommissioning and disposal 4 4 1 Decommissioning X X When decommissioning the interface module follow the installation sequence in reverse order X X Dispose of the interface module correctly 4 4 2 Disposal and recycling Appliance At the end of its service life do not dispose of the interface module in the household w...

Page 12: ...n on the WOLF Link home or WOLF Link pro for 3 5 seconds within 30 seconds Release when the yellow and green LEDs start flashing The red LED on the interface module will start flashing rapidly if it stays on the connection has been established 6 After approx 1 minute the yellow LED will remain on and a connection can be established via the home network 5 1 3 Please refer to www wolf smartset com f...

Reviews: