MOTUS®C14 Operating Instructions
Page
70
of
73
94 762 000 B
Revision 03.2022
21.4.6 Single-Phase Operation
– Configuration L3
ISDU-
Index
Name
Datatype
Length
(Bytes)
Description
Access
259
Nominal current
uint8
1
Unit in 100mA
Maximum value:
26: 2,6A device
66: 6,6A device
Read
Write
262
Trip class
uint8
1
0: 2E
1: 3
2: 5
3: 10A
4: 10
5: 20
6: 30
7: 40E
Read
Write
266
Undercurrent
detection
– Enable
uint8
1
0: Disabled
1: Enabled
Read
Write
270
Undercurrent
detection
–
Threshold
uint8
1
Unit in 100mA
Maximum value:
Actual set nominal
current
Read
Write
274
Undercurrent
detection
– Fault
Type
uint8
1
0: Warning
1: Error
Read
Write
278
Undervoltage
detection
– Enable
uint8
1
0: Disabled
1: Enabled
Read
Write
282
Undervoltage
detection
–
Threshold
uint16
2
Unit in 10mV
Maximum value:
600V
Read
Write
286
Undervoltage
detection
– Fault
Type
uint8
1
0: Warning
1: Error
Read
Write
290
Overvoltage
detection
– Enable
uint8
1
0: Disabled
1: Enabled
Read
Write
294
Overvoltage
detection
–
Threshold
uint16
2
Unit in 10mV
Maximum value:
600V
Read
Write
298
Overvoltage
detection
– Fault
Type
uint8
1
0: Warning
1: Error
Read
Write
21.5 System Commands
– IO-Link-Standard
The commands listed below are specified by the IO-Link specification and implemented in the device:
Command
Name
128
Device Reset
129
Application Reset
130
Restore factory settings