GMG-K / GMG-L Operation manual
Page 29 of 58
B0793 / B0796
Parameters for the upper element row:
P12 Setting of cycle time in hours (0
… 255) in time mode
P13 Setting of cycle time in minutes (0
… 59) in time mode
P14 Setting of external machine pulses (1
… 9999) in pulse mode
P15 Pump delivery switch-off via the number of distributor pulses
(ON = 001 / OFF = 000)
P16 Number of distributor pulses until pump delivery switch-off (1
… 999)
P17 Distributor monitoring ON = 001 / OFF = 000
P18 Setting of delivery time in hours (0
… 100)
P19 Setting of delivery time in minutes (0
… 59)
Note!
The cycle time comprises the duration of the delivery interval and
the off-duty time.
For the two-row pump unit, you can enter the switch-on parameters (length of cycle time or
number of machine pulses) for the lower and upper element row separately. In case of
switch-on parameter overlapping during operation, the delivery by the running row of
elements will be stopped first. Then, the other row of elements starts delivery. Counting is
restarted upon end of delivery each.
Note!
It is not possible to switch on either row of elements via cycle time
and the other one via external machine pulses!
Note!
The sum of the delivery times of the lower and upper element rows
must be less than the smallest cycle time set (lower or upper
element row).
During menu run, the following data is displayed:
1. Display of the menu item
2. Adjustable maximum value
3. Value set
7.1.1 Control operation
After long pressing (>1 s) of [MODE], the menu item "CODE" appears. Upon entry of the
password (numerical password, preset to "1234"), you have access to the menu.
When pressing [MODE] repeatedly, you can switch from one menu item to the next.
Depending on the setting selected, non-relevant menu items will be suppressed.
1
2
3