30
Troubleshooting guide
•
Status-LED does not light up
Check for correct connection and specification of the power adapter.
Ensure that the original power adapter is used.
Specifications: 9 V / DC, 1.3 A
Polarity:
•
No Flame
In case of ignition or flame faliure check if the burner tube is clogged.
Verify the input pressure of the used gas. Ensure that the correct
nozzle is installed in the unit.
N/55
: natural gas, 18 - 25 mbar
P/34: propane / butane gas 47.5 - 57.5 mbar
•
The foot pedal or external IR-motion sensor does not work
Check for correct connection of the cable. Ensure that the socket
and plug is not twisted or broken.
•
Status-LED flashes orange (BHC)
Take care that there are no liquids or other substances at
the Bypass (area between the inner and the outer ring at
the upper part of the burner tube
(5)
). Especially remove
substances in the marked areas at the electrodes. If there
are contaminants in this area, the flame cannot encircle
the electrodes correctly. Clean this areas with a brush.
The burner tube can be cleaned with customary commer-
cial disinfectants, or it can be sterilized in an autoclave or
washed in a dishwasher
(see paragraph 6.1)
.
Bypass
Electrode
• In operating mode "Button" and "Pedal Standard" the flame only burns 30 seconds
BHC time limit is active, Status-LED “ is flashimg amber. The burner
tube is clogged and must be cleaned
(see paragraph 4.1 and 6.1)
.
•
Flame too small / large / soft
Check the position of the air and gas adjustment.
Check if the correct nozzle is installed.
N/55
: natural gas, 18 - 25 mbar
P/34: propane / butane gas, 47.5 - 57.5 mbar
Check if the drilling of the active nozzle is blocked. Unscew the active
nozzle
(see paragraph 1.1)
. If the drilling is blocked clean with a
brush or compressed air.
•
The burner shuts-off due to overtemperature frequently
In case of overtemperature increase the air ventilation or change the
operation site
(see paragraph 5.3)
.
Summary of Contents for Flame100
Page 50: ...50 Notizen Notes Notation...
Page 51: ...51 Notizen Notes Notation...