Drive - Instruction Manual
5 INSTRUCTION WITHOUT HANDSET
Display in Automatic and Manual Mode
5.1 AUTOMATIC MODE “AUTO”
•
When the Door Controller is working in automatic mode the “AUTO” red led is on, whereas the other two red leds are off.
•
When the Door Controller is switched on, or after a self-resetting, it starts directly in the automatic mode.
•
All the signals sent by the main lift controller and by the external devices (barriers, photocells, etc.) are active in this mode.
•
Key 2: keep pressed for at least 3 sec. to check the last alarm code
•
Key 3: keep pressed for at least 3 sec to reset last alarm
•
Key 2+Key3: press together for at least 5 sec to perform the "reset speed profile" operation
•
Key 1: selects Self Learning Cycle.
•
When Key 4 is kept pressed for a while, the Door Controller (ca. 3 sec.), switches to the manual mode “MAN”.
5.2 MANUAL MODE “MAN”
•
When the Door Controller is working in manual mode the “MAN” red led is on, whereas the other two red leds are off.
•
All signals coming from the main lift controller and from other external devices are ignored.
•
The IM contact is deactivated, therefore the Door Controller does not recognize any signal coming from the external devices to
reverse door movement, such as photocells or barriers.
•
Opening and Closing commands may be manually input by pushing Key 2 (open) or Key 3 (close).
•
Key 1 selects Self Learning Cycle.
•
When key 4 is kept pressed for a while (Appx. 3 sec.), the Door Controller switches to the automatic mode “AUTO”.
•
If no keys are pressed the Door Controllerremains in manual mode.
Both in automatic and manual mode the Door Controller will show the following display:
Door opening (Flashing Display)
Door open
Door closing (Flashing Display)
Door Closed
Self learning
Forced closing
It signals an alarm and flashes giving the code of the
recognised alarm.
Reversing system on
Waiting commands from MLC