MIX TARGET
(See fig. n)
1) Go to the OUTDR DSGN item field in the ADJUST Menu
2) Set the OUTDR DSGN setting to OFF
3) Go to the MIX TARGET item field in the ADJUST Menu
4) Set to MIX TARGET to the desired setpoint temperature
RANGE: OFF, 60 to 200°F (16 to 93°C)
DEFAULT: 110°F (43°C)
OUTDOOR DESIGN TEMPERATURE
(OUTDR DSGN)
(See fig. o)
1) Go to the OUTDR DSGN item field in the ADJUST Menu
2) Set to OFF
RANGE: Must be set to OFF in this mode
DEFAULT: 10°F (-12°C)
MOTOR SPEED
(See fig. p)
1) Go to Motor Speed item field in Adjust Menu
2) Set the time the actuating motor requires to operate from
fully closed to fully open
RANGE: 30 to 230 sec
DEFAULT: 150 sec
BOILER MINIMUM TEMPERATURE (Boil MIN)
(See fig. q)
1) Go to the BOIL MIN item field in the ADJUST Menu
2) Set to the minimum boiler return water temperature
recommended by the boiler’s manufacturer
RANGE: OFF or 80 to 180°F (OFF or 27 to 82°C)
DEFAULT: 130°F (54°C)
NOTE:
If the installed boiler is designed for
low return temperature operations, set the
BOIL MIN to OFF.
SETPOINT MODE
29
PROGRAMMING
PROGRAMMING - Step 1 - Programming the Control
n
o
q
p
Summary of Contents for proMIX 101
Page 1: ...proMIX 101 Installation Manual...
Page 4: ...2 INTRODUCTION INTRODUCTION Control Overview...
Page 46: ...44 APPENDIX I proMIX 101 Menu Tree APPENDIX I...
Page 47: ...45 APPENDIX I proMIX 101 Menu Tree APPENDIX I...
Page 48: ...46 APPENDIX II Application Drawings APPENDIX II...
Page 49: ...47 APPENDIX II Application Drawings APPENDIX II...
Page 50: ...48 APPENDIX II APPENDIX II Application Drawings...
Page 51: ...49 APPENDIX II APPENDIX II Application Drawings...
Page 55: ......