Test The Power Supply
1) Make sure exposed wires and bare terminals are not in
contact with other wires or grounded surfaces
2) Turn on the power and measure the voltage between the
Power L and Power N terminals (3 and 4) using an AC
voltmeter, the reading should be between 108 and 132 VAC
Test The Powered Demand Inputs
Voltage Readings for Demand Devices
(described below)
1) When a demand device calls for heat, you should measure
between 20 and 260 VAC at the terminals
2) When off, you should measure less than 5 VAC
Mixing Demand
• Measure voltage between Mix Demand terminals (1 and 2)
21