5
For the Installer
2.2 Taking into the building and installing
The appliance must be taken into the building and installed without subjecting it to significant knocks and jolts,
in order to avoid damaging the combustion chamber and/or the parts slipping. The warranty will be invalidat-
ed if the appliance is damaged due to having been taken into the building and installed incorrectly or if the appli-
ance malfunctions as a consequence of this.
2.2.1 Taking into the boiler room/installation room
The LogWIN may only be transported upright and without cladding and it is easiest to transport using a lift truck
or by rolling on pipes. There is a crane lug on the top of the boiler for transport using hoisting winches. When
transporting via stairs and the such like, the boiler must be suitably secured. Also refer to the technical data in
section 4.4 for transport dimensions.
Tip:
: The weight can be reduced by approx. 130 kg by removing parts which are easy to disassemble (e.g. doors,
hook-in plates, burnthrough plates, heating surface cleaning etc.).
2.2.2 Installing in the boiler room/installation room
The boiler can be installed directly on a non-flammable surface and does not require special foundations.
2.2.3 Note before connection
Move the boiler to its definitive installation position and use the set screws to align it inclined slightly upwards
towards the rear.
Tip:
Before connecting the heating system, install the insulation, flue outlets and rear wall – see section 2.5.
Please note:
–
The minimum clearances for connections, cleaning and maintenance should be observed – see section 2.2.4.
–
Set up the boiler only in a dry area.
–
Follow local regulations and guidelines regarding the boiler room/installation room.
–
Sufficient ventilation of the set-up area must be assured.
Air consumption:
LWP 18 kW:
approx. 40 m
3
/h
LWP 25 kW:
approx. 55 m
3
/h
LWP 30 kW:
approx. 70 m
3
/h
LWP 36 kW:
approx. 80 m
3
/h
LWP 50 kW:
approx. 110 m
3
/h
The combustion air must be free from halogens and hydrocarbons (detergents, e.g. washing
machine) otherwise malfunctions may occur.