INTRODUCTION
TESTING POLICY
Before any generator is shipped from the factory, it is fully
checked for performance. The generator is loaded to its
full capacity, and the voltage, current, and frequency are
carefully checked.
Rated output of generator is based on engineering tests
of typical units, and is subject to, and limited by, the
temperature, altitude, fuel, and other conditions specified
by the manufacturer of applicable engines.
INTENDED USES
This engine generator set has been designed primarily
for portable heavy duty commercial use. This portable
unit requires large quantities of fresh air for cooling the
engine and generator. For safety, long life and adequate
performance, these units should never be run in small
compartments without positive fresh air flow.
RESTRICTED USES
DO NOT remove from the cradle assembly. Removal of the
generator from the cradle assembly may cause excessive
vibration and damage to the engine-generator set.
DO NOT operate and/or store the unit outside during
inclement weather without adequate protection from the
elements. Failure to do so will damage the unit.
DO NOT install and operate this generator in a small
compartment., i.e. generator compartments of vehicles,
motor homes or travel trailers. These compartments
will not allow enough free flow of fresh air to reach the
engine generator set for cooling and will cause the unit to
overheat, damaging both the engine and generator. Small
compartments will also develop hot spots where there is
very little air flow and may cause a fire.
PLEASE NOTE There are 3rd party companies making
enclosures for generators that have been properly
engineered. The use of these 3rd party enclosures is
acceptable as long as they have been certified and meet
current code.
DO NOT attempt to operate at 50 cycles. These units are
designed and governed to operate at 60 cycles only.
SPECIFICATIONS
WL12000HE-04/A
Volts 120/208
3PH
Surge
Watts
12,000
Continuous Watts 10,800
Amps @ 1.0 PF
30
Amps @ 0.8 PF
37.5
WL12000HE-17/A
Volts 132/230
3PH
Surge
Watts
12,000
Continuous Watts 10,800
Amps @ 1.0 PF
27
Amps @ 0.8 PF
34
WL12000HE-18/A
Volts 277/480
3PH
Surge
Watts
12,000
Continuous Watts 10,800
Amps @ 1.0 PF
13
Amps @ 0.8 PF
16
GENERATOR
120/208 & 132/230
Generator Manufacturer
Mecc Alte Spa
Generator Model Number ET20F-200
Part
Number 16346-037
Rotor
13.074
Ohms
Stator Resistance
0.16 Ohms
AVR ASR
277/480
Generator Manufacturer
Mecc Alte Spa
Generator Model Number ET20F-200
Part
Number 16346-038
Rotor
13.309
Ohms
Stator Resistance
1.049 Ohms
AVR ASR
ENGINE
Engine Manufacturer
Honda
Engine Model Number
GX630RH
Type VXE1
NH1
Code GCAMH
Spark Plug Gap
0.030 in
Intake Valve Clearance
0.006 - 0.010 in
Exhaust Valve Clearance
0.010 - 0.012 in
Oil Capacity
57 - 58 oz (1.78 - 1.81 qts)