background image

10

REV C 

60706-241

SYMPTOM

POSSIBLE CAUSE

CORRECTIVE ACTION

Low Output Voltage

1. Undersized/overloaded.

2. Defective governor.

3. Low power - worn engine.

4. High line loss. Indicated by lower voltage at 

load than at generator terminals.

5. Shorted or grounded rotor coil.

6. Defective stator.

7. Underspeed

1.Check for overload on the tractor or undersized.

2. Check tractor governor. Tight or defective throttle 

  levers and joints.

3. Worn or defective tractor engine.

4. Increase size of line wiring. Might also be the result of 

  loose connection indicated by excessive heating at the 

  loose connection terminal.

5. Test and replace if defective.

6.Repair or replace as required.

7. Verify frequency is between 59-61 Hz 

High Output Voltage

Generator is spinning too fast, slows prime mover 

down.

Readjust or replace as required.

Excessive Heating

Clogged ventilating inlet and/or outlet

Clean screens, make sure interior of generator is 

unobstructed.

No Output Voltage

1. Broken or corroded connection

2. Defective diode(s) on rotor.

3. Open exciter circuit in stator.

4. Grounded or shorted rotor winding.

5. Loss of residual magnetism. Usually occurs 

  only after disassembly of field frame or severe 

  mechanical stress/abuse.

6. Shorted stator winding. This can be identified 

  by the use of an internal “growler” at a 

  competent rewinding shop.

7. Grounded stator. Check winding by test lamp 

  or high potential tester from stator leads to 

 lamination.

8. Open stator circuit. Measure circuit between 

  leads with an ohmmeter. Should have a circuit 

  between any pair of leads.

9. Defective Capacitors.

1. Clean and tighten generator and receptacle 

 connections.

2. Replace defective diode(s).

3. Repair or replace stator assembly.

4. Replace grounded rotor assembly.

5. Back flash the 120 Volt circuit with 12 Volts DC

6. Replace stator. )Include generator model and serial 

  number on the order).

7. Same as #6.

8. Same as #6.

9. Test and replace if defective.

Voltage Unsteady/Lights 

Flickering

1. PTO drive line off alignment.

2. Drive line knuckles out of sync.

1. Realign within 5 degrees.

2. Re-sync drive line halves.

TROUBLE SHOOTING TABLE

Summary of Contents for W10PTOS

Page 1: ...WINCO INC 225 S CORDOVA AVE LE CENTER MN 56057 507 357 6821 SERVICE DEPT 507 357 6831 www wincogen com INSTALLATION AND OPERATORS W10PTOS A W15PTOS F GENERATORS MANUAL...

Page 2: ...______________ PURCHASE DATE _________________________________________ DEALER NAME ___________________________________________ DEALER PHONE ________________________________________ SAVE THESE INSTRUCT...

Page 3: ...nt to mount it This generator includes a color coded voltmeter to warn against high or low voltage and two output power receptacles with individual circuit breakers for your protection To reduce maint...

Page 4: ...running E Never wear a necktie loose articles of clothing or anything else that can be caught in moving parts F Never try to stop drive shaft with your hand or your foot SAFETY IMPORTANT SAFETY INSTR...

Page 5: ...PMENT DAMAGE When using the 3 point hitch assembly all three points must be attached to the tractor Failure to do so will cause the generator to tip when lifting it damaging both the t bar and the gen...

Page 6: ...e the commercial power lines from the load and the generator when the generator is supplying power See the following diagrams A properly rated and installed double throw manual power isolation transfe...

Page 7: ...RSONAL INJURY IF THE GENERATOR IS TO BE USED AS A STANDBY POWER SOURCE A MANUAL TRANSFER SWITCH MUST BE INSTALLED TO SEPARATE THE GENERATOR AND THE COMMERCIAL POWER LINES THE SWITCH MUST ISOLATE THE G...

Page 8: ...the generator with the drive shaft tumbling bar Couple the tumbling bar to the generator input shaft first then to the power take off shaft Check alignment tractor power take off shaft tumbling bar an...

Page 9: ...tored on end provided the generator is on a clean dry elevated surface such as a board Do not have it resting on a dirt surface Figure 3 MAINTENANCE REQUIREMENTS LUBRICATION 1 Check the generator gear...

Page 10: ...put Voltage 1 Broken or corroded connection 2 Defective diode s on rotor 3 Open exciter circuit in stator 4 Grounded or shorted rotor winding 5 Loss of residual magnetism Usually occurs only after dis...

Page 11: ...BREAKER G GROUND LUG 20 AMP RCPT G1 G1 G3 G3 2 3 1 4 N G BOND W10PTO WIRING DIAGRAM WIRING DIAGRAMS W1 V1 U1 W2 V2 U2 ON OFF H H N GND G1 G3 H N VOLTMETER GENERATOR 20A BREAKER 60 AMP RCPT 60A 240V B...

Page 12: ...nd fitness for a particular purpose are limited to 12 months or 1000 hours which ever occurs first from date of purchase In no event is WINCO liable for incidental or consequential damages Note Some s...

Reviews: