INTRODUCTION

The WINCO rotating field power take-off generators are designed 

primarily for hobby/small farm use as a standby electrical power supply, 

utilizing the power take-off of a tractor or truck as the prime mover. 

This PTO drive generator will provide 120/240V single phase, 60Hz 

electrical service when properly driven.

NOTE: The prime mover which drives the generator must be capable 

of delivering approximately 2 HP per 1000 watts output from the 

generator. Observe input RPM specifications.

This generator may be mounted in many different fashions. The three 

most popular are foundation mounted, trailer mount or 3-point hitch 

mounted. Your application will dictate how you may want to mount it.

This generator includes a color coded voltmeter to warn against high 

or low voltage, and two output power receptacles with individual 

circuit breakers for your protection. To reduce maintenance problems, 

the coupling between the generator input shaft and rotor consists of 

precision helical gearing rather than a chain link drive.

IMPORTANT:

THE MANUFACTURER STRONGLY RECOMMENDS RUNNING THE 

GENERATOR UNDER LOAD AT LEAST ONCE A MONTH IN ORDER 

TO EVAPORATE ANY ACCUMULATED MOISTURE CONDENSATION 

AND TO KEEP THE UNIT IN GOOD WORKING ORDER.

SPECIFICATIONS

W10PTOS

Watts     10,000

Amps     41.6

Input 

Speed 

   515 

RPM

Generator Speed   

 

3600 RPM

Input Shaft   

 

 

1 3/8” - 6 spline

Required Tractor PTO HP  20

Gear Lube

 

Volume    16 

oz

 

Type 

    85/90W-140

W15PTOS

Watts     15,000

Amps     62.5

Input 

Speed 

   515 

RPM

Generator Speed   

 

3600 RPM

Input Shaft   

 

 

1 3/8” - 6 spline

Required Tractor PTO HP  30

Gear Lube

 

Volume    16 

oz

 

Type 

    85/90W-140

Summary of Contents for W10PTOS

Page 1: ...WINCO INC 225 S CORDOVA AVE LE CENTER MN 56057 507 357 6821 SERVICE DEPT 507 357 6831 www wincogen com INSTALLATION AND OPERATORS W10PTOS A W15PTOS F GENERATORS MANUAL...

Page 2: ...______________ PURCHASE DATE _________________________________________ DEALER NAME ___________________________________________ DEALER PHONE ________________________________________ SAVE THESE INSTRUCT...

Page 3: ...nt to mount it This generator includes a color coded voltmeter to warn against high or low voltage and two output power receptacles with individual circuit breakers for your protection To reduce maint...

Page 4: ...running E Never wear a necktie loose articles of clothing or anything else that can be caught in moving parts F Never try to stop drive shaft with your hand or your foot SAFETY IMPORTANT SAFETY INSTR...

Page 5: ...PMENT DAMAGE When using the 3 point hitch assembly all three points must be attached to the tractor Failure to do so will cause the generator to tip when lifting it damaging both the t bar and the gen...

Page 6: ...e the commercial power lines from the load and the generator when the generator is supplying power See the following diagrams A properly rated and installed double throw manual power isolation transfe...

Page 7: ...RSONAL INJURY IF THE GENERATOR IS TO BE USED AS A STANDBY POWER SOURCE A MANUAL TRANSFER SWITCH MUST BE INSTALLED TO SEPARATE THE GENERATOR AND THE COMMERCIAL POWER LINES THE SWITCH MUST ISOLATE THE G...

Page 8: ...the generator with the drive shaft tumbling bar Couple the tumbling bar to the generator input shaft first then to the power take off shaft Check alignment tractor power take off shaft tumbling bar an...

Page 9: ...tored on end provided the generator is on a clean dry elevated surface such as a board Do not have it resting on a dirt surface Figure 3 MAINTENANCE REQUIREMENTS LUBRICATION 1 Check the generator gear...

Page 10: ...put Voltage 1 Broken or corroded connection 2 Defective diode s on rotor 3 Open exciter circuit in stator 4 Grounded or shorted rotor winding 5 Loss of residual magnetism Usually occurs only after dis...

Page 11: ...BREAKER G GROUND LUG 20 AMP RCPT G1 G1 G3 G3 2 3 1 4 N G BOND W10PTO WIRING DIAGRAM WIRING DIAGRAMS W1 V1 U1 W2 V2 U2 ON OFF H H N GND G1 G3 H N VOLTMETER GENERATOR 20A BREAKER 60 AMP RCPT 60A 240V B...

Page 12: ...nd fitness for a particular purpose are limited to 12 months or 1000 hours which ever occurs first from date of purchase In no event is WINCO liable for incidental or consequential damages Note Some s...

Reviews: