5. Shut off the engine.

4. Disconnect drive shaft (tumbling bar) power take-off end
first, then generator end.

MAINTENANCE

The following chart lists various symptoms of poor generator
operation with possible causes for them and the appropriate
corrective action. You will need a volt-ohm meter or test light to
check some of the causes. For some of the other causes you
will need to check generator speed. To check the generator
speed you can use the frequency meter on the generator
control panel.

CAUTION: Equipment Damage

Most electrical equipment in North America operates satisfac-
torily at frequencies between 59 and 61 Hz (cycles per
second.) Operating the generator at frequencies outside that
range may cause damage to the generator and/or to electrical
equipment driven by the generator.

GENERAL

Routine preventive maintenance minimizes costly repairs and
generator downtime. Before each use, inspect the generator:
gear case oil level should be correct, cooling vents and
screens should be clear, and generator mounting hardware
should be tight. Clean and inspect the generator after storing it
for long periods, and after using it in extremely dusty condi-
tions or in severe weather, such as rain or blowing snow.

LUBRICATION

The generator bearings are factory lubricated and sealed, and
require no further lubrication.

The splined generator input shaft should be cleaned and
lubricated with a thin film of grease before and after each use
of the generator.

The drive shaft (tumbling bar) requires greasing. Keep the
universal joints in the coupling shaft free from grease and dirt
buildup.

NOTE:

Do not over lubricate the universal joints.

See Figure 8 for recommended lubrication schedule for the
coupling shaft.

Check the generator gear case oil level before each use of the
generator. Maintain the oil level at oil level plug height. (Figure
6 illustrates oil level plug location.) The generator is shipped
with lubricant in the gear case. Specifications for gear case
lubricant are:

API Service: GL-5
Grade: SAE 85W-9O-140
Amount: 1 pint

The following kinds of oil are recommended for use in the
generator gear case: Mobil SAE 85W90-140 API Service GL-5,
Sunoco/DX XL80W90-140 Kendal Three Star 85W-140,
Amoco 85W140 or equivalent.

CAUTION: Equipment Damage

Do not overfill generator gear case. Overfilling causes over-
heating and oil seal failure.

Change the oil at least once every six months. Change it more
often if you use the generator in bad weather. Use the follow-
ing procedure to change generator gear case oil (see Figure
6):

1. Remove gear case breather. Soak breather in cleaning
solvent, then allow it to dry.

2. Remove oil level check plug.

3. Remove the oil drain plug, drain the oil into a clean oil
resistant container, 1 quart or larger. Check the oil for metal.
Fine metal dust in the oil does not indicate trouble, but metal
chips do. Dismantle the gear case and look for damaged
gears if you find metal chips in the oil.

4. Replace the oil drain plug. Refill the gear case through the
breather port with new oil of the recommended type. Fill the
case up to oil level check plug height. (It will take about 1 pint.)

Figure 8

Summary of Contents for W100PTO

Page 1: ...EV 3 W85PTOS W100PTO W105PTOT W135PTOS W145PTOT W150PTOS W165PTOT Tractor Drive PTO Generators OWNERS MANUAL INSTALLATION AND OPERATION INSTRUCTIONS SAFETY FIRST READ THIS MANUAL BEFORE OPERATING YOUR...

Page 2: ...ION 5 Pre Start Checks 5 Starting Procedure 6 Stopping 6 MAINTENANCE 7 Lubrication 7 Cleaning 8 Storage 8 TroubleShootingTable 8 GENERATORCONNECTIONS 120 240 Volt Single Phase 10 120 240 Volt Three Ph...

Page 3: ...ion and or fire a Keep a fire extinguisher nearby and know its proper use Fire extinguishers rated ABC by NFPA are appropriate 3 DEADLY EXHAUST GAS Exhaust fumes from any engine contain carbon monoxid...

Page 4: ...carton with the large carton 4 Open the subpack carton and make sure it contains a Generator instruction manual b Load disconnect plug disassembled in bag 5 Remove the four bolts which hold down the...

Page 5: ...less than 15 degrees during generator operation even though the mechanical design of the tumbling bar would allow greater misalignment The following wire sizes are recommended for each unit Generator...

Page 6: ...ans should install electrical wiring Wiring must conform to all applicable national state and local codes Reference National Fire Protection Association Manual No 70 National Electrical Code DANGER PE...

Page 7: ...t its starting current which is a lot higher Motor starting current requirements vary greatly by motor size and type Repulsion induction type motors are the easiest to start typically using 1 1 2 to 2...

Page 8: ...OTE EquipmentDamage If the load includes motors turn them on one at a time highest starting current motor first next highest second etc Adjust engine throttle to keep generator output under load at 60...

Page 9: ...the generator The drive shaft tumbling bar requires greasing Keep the universal joints in the coupling shaft free from grease and dirt buildup NOTE Do not over lubricate the universal joints See Figur...

Page 10: ...erloaded 2 Reduce load if it is higher than the rated capacity of the generator See generator nameplate 3 Inadequate engine horsepower 3 Generator requires 2 HP 1000 watts output Obtain larger engine...

Page 11: ...wer take off misalignment 1 Correct misalignment It should be less than 15 degrees vibration excessive 2 Loose mounting nuts and bolts 2 Tighten mounting nuts and bolts repair hold down stud or hold d...

Page 12: ...Page 10 60706 160REV3 3117 30 GENERATOR CONNECTIONS 120 240 VOLT SINGLEPHASE GENERATOR CONNECTIONS 120 240 VOLT THREEPHASE...

Page 13: ...Page 11 60706 160REV3 3117 30 GENERATOR CONNECTIONS 120 208 VOLT THREEPHASE GENERATOR CONNECTIONS 277 480 VOLT THREEPHASE...

Page 14: ...Page 12 60706 160REV3 3117 30 GENERATOR RECEPTACLE PANEL W105PTOT 4 W105PTOT 17 GENERATOR RECEPTACLE PANEL W85PTOS 3 W100PTOS 3 GENERATOR RECEPTACLE PANEL W105PTOT 18...

Page 15: ...EV3 3117 30 GENERATOR RECEPTACLE PANEL ON MODELS W135PTOS 3 W145PTOT 4 W145PTOT 17 W150PTOS 3 GENERATOR RECEPTACLE PANEL ON MODEL W165PTOT 18 GENERATOR CONVENIENCE RECEPTACLE WIRING ON ALL MODELS EXCE...

Page 16: ...limitationsonthedurationofanimpliedwarranty andsomestatesdonotallow the exclusion or limitation of incidental or consequential damages so that above limitation or exclusion may notapplytoyou Thiswarra...

Reviews: