Winco W100PTO Owner'S Manual Download Page 5

Page 3

60706-160 REV 3

3117-30

A. The foundation location should enable aligning the drive
shaft (tumbling bar) in a straight or nearly straight line be-
tween the power take-off and the generator input shaft.
Misalignment must be less than 15 degrees during generator
operation, even though the mechanical design of the tumbling
bar may allow greater misalignment.

B. The foundation must be solid enough to absorb generator
starting and reflected load torque during operation.

C. The foundation surface should be flat.

D. Space is required around the generator for mounting
switching devices, making connections, and for servicing.

E. All four generator mounting pads must rest firmly on the
foundation. Install shims if necessary to even out the founda-
tion under the mounting pads then bolt the generator firmly in
place.

TRAILER MOUNTING

Mount the generator on a trailer if you plan to use it as a
portable power source. See Figure 3. When selecting or
building a trailer to mount the generator, consider the
following points:

Trailer, for Portable Operation

A. The trailer construction must be strong enough to support
the generator.

B. The design of the trailer must enable the trailer to remain
stable during operation, and to resist tipping caused by
generator starting and reflected load torque.

WARNING: Personal Injury & Equipment Damage

TRAILER MAY TIP OVER AND CAUSE INJURIES IF
WHEELS ARE NOT SPACED FAR ENOUGH APART.

C. The trailer height and mounting position of the generator on
the trailer should enable aligning the drive shaft (tumbling bar)
in a straight or nearly straight line between the power take-off
and generator input shafts. Misalignment must be less than
15 degrees during generator operation, even though the
mechanical design of the tumbling bar would allow greater
misalignment.

The following wire sizes are recommended for each unit.

Generator

Size

Model

AWG

Insulation

W85PTOS

4/0

Neoprene/THHN

W100PTOS

4/0

Neoprene/THHN

W105PTOT

4/0

Neoprene/THHN

W135PTOS

350MCM

THHN

NO Plug Provided

W145PTOT

4/0

THHN

NO Plug Provided

W150PTOS

500MCM

THHN

NO Plug Provided

W165PTOT

1/0

THHN

NO Plug Provided

WARNING: Equipment Damage

Never use acid core solder.  When soldering insure no excess
solder runs down on the contact surface - Solder on the contact
surface will not allow the contacts to mate properly causing
them to burn up.

Each wire should be stripped back 7/8 of an inch and inserted
into one of the contacts in the plug kit.  You will then either need
to solder them together using a good grade of resin core
solder or they can be crimped with an appropriate compres-
sion crimper or both.

Approved Crimping tools are:

1. Anderson Power Products
2. ETC Model HHS hydraulic crimper
3. ITT Blackburn NO. 1640
4. T&B (Thomas & Betts) #TBM5

To complete the assembly of the disconnect plug refer to the
instruction sheet in the plug kit.

WARNING: Electrical Shock

DURING THE NEXT STEP, THE LOAD DISCONNECT PLUG
SHOULD NOT BE PLUGGED INTO ITS RECEPTACLE. ALSO,
MAKE SURE THAT THE EQUIPMENT TO WHICH THE PLUG
LEADS (CABLES) ARE BEING CONNECTED IS NOT ENER-
GIZED (LIVE).

8. Strip the insulation off the free end of each of the plug leads
(cables), and connect them to the load transfer switch (or
directly to the load).

Installation

FOUNDATION MOUNTING

Mount the generator on a foundation if it is to be used as a
permanent or standby power source (see Figure 2). See
“TRAILER MOUNTING” if generator will be used as a portable
power source (see Figure 3). When planning a foundation
consider the following points:

Figure 2

Figure 3

Summary of Contents for W100PTO

Page 1: ...EV 3 W85PTOS W100PTO W105PTOT W135PTOS W145PTOT W150PTOS W165PTOT Tractor Drive PTO Generators OWNERS MANUAL INSTALLATION AND OPERATION INSTRUCTIONS SAFETY FIRST READ THIS MANUAL BEFORE OPERATING YOUR...

Page 2: ...ION 5 Pre Start Checks 5 Starting Procedure 6 Stopping 6 MAINTENANCE 7 Lubrication 7 Cleaning 8 Storage 8 TroubleShootingTable 8 GENERATORCONNECTIONS 120 240 Volt Single Phase 10 120 240 Volt Three Ph...

Page 3: ...ion and or fire a Keep a fire extinguisher nearby and know its proper use Fire extinguishers rated ABC by NFPA are appropriate 3 DEADLY EXHAUST GAS Exhaust fumes from any engine contain carbon monoxid...

Page 4: ...carton with the large carton 4 Open the subpack carton and make sure it contains a Generator instruction manual b Load disconnect plug disassembled in bag 5 Remove the four bolts which hold down the...

Page 5: ...less than 15 degrees during generator operation even though the mechanical design of the tumbling bar would allow greater misalignment The following wire sizes are recommended for each unit Generator...

Page 6: ...ans should install electrical wiring Wiring must conform to all applicable national state and local codes Reference National Fire Protection Association Manual No 70 National Electrical Code DANGER PE...

Page 7: ...t its starting current which is a lot higher Motor starting current requirements vary greatly by motor size and type Repulsion induction type motors are the easiest to start typically using 1 1 2 to 2...

Page 8: ...OTE EquipmentDamage If the load includes motors turn them on one at a time highest starting current motor first next highest second etc Adjust engine throttle to keep generator output under load at 60...

Page 9: ...the generator The drive shaft tumbling bar requires greasing Keep the universal joints in the coupling shaft free from grease and dirt buildup NOTE Do not over lubricate the universal joints See Figur...

Page 10: ...erloaded 2 Reduce load if it is higher than the rated capacity of the generator See generator nameplate 3 Inadequate engine horsepower 3 Generator requires 2 HP 1000 watts output Obtain larger engine...

Page 11: ...wer take off misalignment 1 Correct misalignment It should be less than 15 degrees vibration excessive 2 Loose mounting nuts and bolts 2 Tighten mounting nuts and bolts repair hold down stud or hold d...

Page 12: ...Page 10 60706 160REV3 3117 30 GENERATOR CONNECTIONS 120 240 VOLT SINGLEPHASE GENERATOR CONNECTIONS 120 240 VOLT THREEPHASE...

Page 13: ...Page 11 60706 160REV3 3117 30 GENERATOR CONNECTIONS 120 208 VOLT THREEPHASE GENERATOR CONNECTIONS 277 480 VOLT THREEPHASE...