background image

5

OPM-128/E

INTRODUCTION

INTENDED USES

This engine generator set has been designed primarily for 

portable heavy duty commercial use. Both 120 volt and 240 

volt receptacles are provided in the control panel to plug 

in your loads (lights, portable tools, and small appliances). 

These units are dual wound generators, therefore the 

120 volt loads must be equally split with 1/2 of the rated 

capacity available on each of the two 120 volt circuits. 

This portable unit requires large quantities of fresh air for 

cooling the engine and generator. For safety, long life and 

adequate performance, these units should never be run in 

small compartments without positive fresh air flow.

RESTRICTED USES

DO NOT 

remove from the cradle assembly. Removal of the 

generator from the cradle assembly may cause excessive 

vibration and damage to the engine-generator set.

DO NOT

 operate and/or store the unit outside during 

inclement weather without adequate protection from the 

elements. Failure to do so will damage the unit.

DO NOT 

install and operate this generator in a small 

compartment., i.e. generator compartments of vehicles, 

motor homes or travel trailers. These compartments 

will not allow enough free flow of fresh air to reach the 

engine generator set for cooling and will cause the unit to 

overheat, damaging both the engine and generator. Small 

compartments will also develop hot spots where there is 

very little air flow and may cause a fire.

PLEASE NOTE

 There are 3rd party companies making 

enclosures for generators that have been properly 

engineered. The use of these 3rd party enclosures is 

acceptable as long as they have been certified and meet 

current code.

DO NOT 

attempt to operate at 50 cycles. These units are 

designed and governed to operate at 60 cycles only.

UNIT CAPABILITIES

GENERATOR CONNECTIONS

DP5000/T: 120 Volt and 240 Volt receptacles are provided 

for connection to various loads. The diagram below 

represents this 4,500 watt (rated output) generator. A & B 

represent the 120 volt output legs of this generator. Up to 

2,250 watts at 120 volts (37.5 Amps) can be drawn from 

the receptacles attached to either A or B output legs. This 

generator is capable of producing 37.5 Amps of 240 volt 

current at C. Check the appliance or tool nameplates for the 

current and voltage to insure compatibility. Remember that 

power taken from C reduces the power available equally at 

both A and B and vice versa.

STARTING ELECTRIC MOTORS

Electric motors require much more current (amps) to start 

them than to run them. Some motors, particularly low cost 

split-phase motors, are very hard  to start and require 5 to 7 

times as much starting current as running current. Capacitor 

motors are easier to start and usually require 2 to 4 times 

as much starting current as running current. Repulsion 

Induction motors are the easiest to start and require only 1 

1/2 to 2 1/2 times as much starting as running current.

Most fractional horsepower motors take about the same 

amount of current to run them whether they are Repulsion 

Induction (RI), Capacitor (Cap), or Split-Phase (SP) type.

If the electric motor is connected to a hard starting load, 

such as an air compressor, it will require more starting 

current. If it is connected to a light load, or no load, such as 

a power saw, it will require less starting current. The exact 

requirement will also vary with the brand or design of the 

motor.

Self-exciting generators respond to severe overloading 

differently than utility power. When overloaded, the engine 

is not able to supply enough power to bring the electric 

motor up to operating speed. The generator responds with 

high initial starting current, but the engine speed drops 

sharply. The overload may stall the engine. If allowed to 

operate at very low speeds, the electric motor starting 

winding will burn out in a short time. The generator 

winding might also be damaged.

CAUTION: EQUIPMENT DAMAGE

Running the generator set under these conditions may 

result in damage to the generator stator as well as the 

motor winding.

The heavy surge of current required for starting motors 

is required for only an instant. The generator will not be 

damaged if it can bring the motor up to speed in a few 

seconds of time. If difficulty is experienced in starting 

motors, turn all other electrical loads off and if possible 

reduce the load on the electric motor.

Summary of Contents for DP5000-03/A

Page 1: ...E No other WINCO generator has the same serial number as yours If you should ever need to contact us on this unit it will help us to respond to your needs faster MODEL __________________________________________________ SERIAL NUMBER _________________________________________ PURCHASE DATE _________________________________________ DEALER NAME ___________________________________________ DEALER PHONE ...

Page 2: ...R GENERATOR MAINTENANCE CLEANING TROUBLESHOOTING 14 RECEPTACLE WIRING DIAGRAM 15 36 MONTH LIMITED WARRANTY 16 CA EMISSION CONTROL WARRANTY 16 SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and maintenance of the generator Read and understand all instructions in the manual before starting and operating the generator USING THIS MANUAL ...

Page 3: ...mber 16346 612 ENGINE Engine Manufacturer Honda Engine Model Number GX270 Type RT2VMT2 Code GCBGT Oil Capacity 38 4 oz 1 2 qts TESTING POLICY Before any generator is shipped from the factory it is fully checked for performance The generator is loaded to its full capacity and the voltage current and frequency are carefully checked Rated output of generator is based on engineering tests of typical u...

Page 4: ...can result in potentially deadly hazards from electrical shock exhaust gas asphyxiation or fire Please read all safety instructions carefully before installation or use Keep these instructions handy for future reference Take special note and follow all warnings on the unit labels and in the manuals CALIFORNIA PROPOSITION 65 WARNING This product contains crude oil gasoline diesel fuel and other pet...

Page 5: ...s can be drawn from the receptacles attached to either A or B output legs This generator is capable of producing 37 5 Amps of 240 volt current at C Check the appliance or tool nameplates for the current and voltage to insure compatibility Remember that power taken from C reduces the power available equally at both A and B and vice versa STARTING ELECTRIC MOTORS Electric motors require much more cu...

Page 6: ...s been out of operation for an extended period of time it is best to drain old fuel from the engine and replace with fresh fuel before attempting to start See the engine manual for special instruction for operating this unit at over 5000 feet PREPARING THE UNIT UNPACKING CAUTION EQUIPMENT DAMAGE THIS UNIT HAS BEEN SHIPPED WITH OIL Failure to maintain the engine oil at the proper level will result ...

Page 7: ...be at the full mark before the engine will start and run BASIC OPERATION 1 Check oil level refill as needed 2 Move the fuel valve lever to the ON position 3 To Start a cold engine move the choke rod to the CLOSED position 4 Move the throttle lever away from the MIN position about 1 3 of the way toward the MAX position 5 Turn the engine switch to the ON position 6 Operate the starter This engine is...

Page 8: ...ither the receptacles or the generator The generator is a limited source of electrical power therefore pay special attention to the receptacle and generator ratings The nameplate rating can be obtained through a single receptacle as long as the receptacles amperage rating is not exceeded CAUTION EQUIPMENT DAMAGE Never permit the choke to remain on after the engine has run for a short time It is no...

Page 9: ...PERSONAL DANGER A fully isolated double pole double throw manual transfer switch must be installed any time a generator is being connected to an existing distribution system 1 These engine generator sets are designed for portable heavy duty commercial use Receptacles are provided on the control panel to permit 120 and 240 Volt portable appliances and tools to be plugged directly into them A 4 wire...

Page 10: ...ad This will ensure the generator is balanced Balanced Unbalanced YOURGEN The WINCO YourGen meter allows you to see useful information about your generator from the front panel by displaying RPMs Voltage frequency load hours and maintenance reminders It also has the ability to display warnings if any parameter gets outside of normal operation range Cycle Button During normal operation the display ...

Page 11: ...equire more frequent oil changes Alarms The display will start blinking and toggle to the first parameter that is out of specification The panel will remain flashing until the fault condition returns to within the acceptable range see following table Acceptable Range Frequency 57 63 Hz Voltage 110VAC 130VAC VAC1 VAC2 220VAC 260VAC Battery When the unit is off the YourGen meter will display the hou...

Page 12: ...ded service period Service more often under dusty conditions WARNING EQUIPMENT DAMAGE Never start or run the engine with the air filter removed This will allow dirt to enter the engine causing rapid engine wear This type of damage is not covered under warranty 1 Unsnap the air cleaner cover clips remove the air cleaner cover and remove the air filter element ENGINE CARE MAINTENANCE SCHEDULE If maj...

Page 13: ...ld be operated every three to four weeks It should be operated for a period of time sufficient to warm the unit up and to dry out any moisture that has accumulated in the windings If left this moisture can cause corrosion in the winding Frequent operation of the engine generator set will also ensure that the set is operating properly should it be needed in an emergency GENERATOR MAINTENANCE Any ma...

Page 14: ...ective capacitor Circuit breaker trips Defective load Defective receptacle Excessive load Problem Possible Causes Voltage too high Engine speed is too high Generator overheating Overloaded Insufficient ventilation No output voltage Short in load disconnect Tripped or defective circuit breaker Broken or loose wire Defective receptacle No residual magnetism in generator Defective stator Defective ro...

Page 15: ...15 OPM 128 E RECEPTACLE WIRING DIAGRAM G2 G2 N N N N N N N G2 G2 G1 G1 G1 G1 GND GND GND GND ...

Page 16: ...be furnished upon request THERE ARE NO EXPRESS WARRANTIES OTHER THAN THOSE DESCRIBED HEREIN THERE ARE NO OTHER WARRANTIES EXPRESSED OR IMPLIED OR OTHERWISE CREATED INCLUDING BUT NOT LIMITED TO WARRANTIES OF MERCHANTABILITY OR WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE WINCO is liable for the repair or replacement of the product only and is not liable for incidental or consequential damages as ...

Reviews: