REV A
OPM-136
in the oil does not indicate trouble, but metal chips do. Dismantle the
gearcase and look for damaged gears if you find metal chips in the oil.
4. Replace the oil drain plug. Refill the gearcase through the breather
port with new oil of the recommended type. Fill the case until a little bit
of oil comes out of oil level check plug hole (it will take less than 1 pint
when dry).
5. Replace the oil level check plug.
6. Replace the breather.
CLEANING & INSPECTION
Use a vacuum cleaner or dry low pressure compressed air (regulated
at 25-35 PSI) to clean the generator periodically.
WARNING:
Do NOT clean the generator while it is running.
Proceed as follows:
1. Remove control box cover. Vacuum or blow dust or debris from the
control box. Inspect all wiring for correct routing, fraying insulation, and
secure connections.
2. Remove end cover. Vacuum or blow dust and debris from the inside
of the generator. Inspect wiring for loose connections, fraying insulation
and correct wire routing.
3. Replace end cover and control box cover.
GENERATOR STORAGE
Before storing the generator, apply a heavy coat of grease to the
splined input shaft. Store the generator in a sheltered area, where it is
protected against snow, rain, and excessive dust.