Installation and operating instructions Wilo-Para
37
en
Preparation
• Never install the pump outside of the building.
• Choose an installation point that is as easily accessible
as possible.
• Observe the pump’s permitted installation
position (Fig. 2) and rotate the motor head (2+5) if
necessary.
• Install shut-off devices upstream and downstream of
the pump to facilitate pump replacement.
• Align the upper shut-off device laterally.
• When installing in the feed of open systems, the
safety supply must branch off upstream of the pump
(EN 12828).
• Complete all welding and brazing work.
• Flush the pipe system.
Rotating the motor
head
Rotate the motor head (2+5) before installing and con
-
necting the pump.
• If necessary, remove the thermal insulation shell.
CAUTION!
An incorrect installation position may damage the
pump.
• Select the installation point according to the permit
-
ted installation position (Fig. 2).
• The motor must always be installed horizontally.
• The electrical connection must never face upwards.
CAUTION!
Leaking water may damage the control module.
• Align the upper shut-off device such that leaking
water cannot drip onto the control module (5).
WARNING!
Risk of fatal injury from magnetic field!
Risk of fatal injury for people with medical implants due
to permanent magnets installed in the pump.
• Never remove the rotor.