background image

English

20

Wilo AG 09/2005

 

6.2.2 Routine inspection (daily/weekly) 

   

a) Check operating behavior. Ensure noise, vibra-
tion and bearing temperatures are normal.
b) Check that there are no abnormal fluid or lubri-
cant leaks (static and dynamic seals) and that any 
sealant systems (if fitted) are full and operating 
normally.
c) Pump fitted with a stuffing box: leakage of 20 
drops per minute.
d) Pump fitted with a mechanical seal: no leakage.
e) Check the level and condition of oil lubricant. 
On grease lubricated pumps, check running hours 
since last recharge of grease or complete grease 
change.

6.2.3 Periodic inspection (six monthly)

    

b) Check pump-running records for hourly usage 
to determine if bearing lubricant requires chan-
ging.
c) The coupling should be checked for correct 
alignment and worn driving elements.
      

Ensure that your equipment corresponds to the 
arrangements of this leaflet.

6.2.4 Mechanical seals

The current maintenance is limited to seal control. 
It is necessary to detect any small leakage which 
announces the beginning of the deterioration of 
friction faces or secondary seal elements (rings, 
bellows, synthetic membranes). It is advisable to 
stop the pump as soon as possible. Have an appro-
ved seal vendor replace or repair the seal.

6.2.5 Gland packing

6.2.5.1 Pump fitted with a packed gland

A well run in and correctly adjusted packing gland 
requires little maintenance.
If, after some time, the leakage becomes too 
great, the gland should be tightened again in order 
to return these to a normal level.
If re-tightening is not possible, new packing must 
be installed.

6.2.5.2 Gland packing inspection and removal

a) Remove the shield guards
b) Slide back the gland
c) Remove the packing rings with an extractor 
designed for this purpose (including the lantern 
ring if it exists; note its position and its direction of 
rotation).
d) Inspect the state of the sleeve surface; the pre-
sence of many marked grooves will indicate that it 
must be replaced.
e) Carefully clean the different pieces of the 
packing gland.

6.2.5.3 Gland packing fitting

If the packing is supplied as cord the packing must 
be cut so that the external diameter is lightly tigh-
tened and there is an initial gap between the 
sleeve and the packing ring.
For that purpose, wind the packing helically 
around the shaft sleeve or a chuck of the same 
diameter. (Take precautions to avoid damaging 
sleeve)  

 

  

Setting of packing

Follow the instructions:
a) Assemble of the packing in S.
b) Stagger by about 90° between two rings.
c) Assemble packing after packing.  

   

The following checks should be made 
and the appropriate action taken to 
remedy any deviations:

a) Check foundation bolts for security of 
attachment and corrosion.

If a check shows a bad running of the 
motor pump unit, the user must:
Refer to the "fault finding chart" chapter 7 
of this leaflet to apply the recommended 
solutions.

CAUTION!

CAUTION!

NOTE:

Ensure a tightening on the stuffing box 
housing and not on the sleeve.

CAUTION!

Summary of Contents for NPG 100-315

Page 1: ...GB Installation and operating instructions Wilo NPG 4095556 Ed_01_gb_0610_Wilo NL NLG NPG www promhimtech ru zakaz promhimtech ru...

Page 2: ...Quality Management System Standards as cer tified and audited by external Quality Assurance organizations Genuineparts andaccessories have been designed tested and incorporated into the products to he...

Page 3: ...us liquids 1 7 Noise level When pump noise level exceeds 85 dBA attention must be given to prevailing Health and Safety Legislation to limit the exposure of plant opera ting personnel to the noise The...

Page 4: ...e which travels through the walls and windows does not generate too high noise levels in the machine room s surroun dings 2 Transport and storage 2 1 Consignment receipt and unpacking Immediately afte...

Page 5: ...lar as possible If necessary a lifting beam can be placed between the winch and the load When heavy pieces are lifted up never stay or work under the load or in the area which could be in the path of...

Page 6: ...ve when in contact with the pump motor unit and its working parts Important for other liquids consult us for preliminary advice The NPG type pump is a single stage pump with axial suction support unde...

Page 7: ...DN 250 DN 300 DN 350 DN 400 DN 500 200 4 6 250 4 4 6 6 300 4 6 315 8 8 12 12 350 4 6 355 8 8 12 12 400 8 8 8 12 12 12 450 8 12 500 16 10 10 10 6 5 4 15 15 15 10 6 650 6 5 10 NPG 200 315 37 4 12 NPG Ty...

Page 8: ...Put shims on the foundation surface approx 20 25 mm thick one on each side of the bolt hole as an alternative leveling screws can be used Lay the base plate and level in both directions with extra sh...

Page 9: ...ent observed on site is due to a wrong adjustment under the base plate disturbed during transport or because of forces exerted by the pipework It is only necessary to rectify the adjustment under base...

Page 10: ...r their sharing out on the pump flanges refer to standard NFCR 13 931 4 4 2 Suction piping 4 4 2 1 Design of a flooded suction line The suction line must be as short and direct as possible never mount...

Page 11: ...sure surge and from reverse rotation If necessary a control manometer can be connec ted on the pipework 4 4 4 Final checks a Check the tightening of anchor bolts Tighten them if necessary b Check that...

Page 12: ...See sections 5 5 4 and 5 5 5 If a defect of cooling can lead to temperature hig her than those acceptable a system of cooling surveillance must be installed Exceptwhenexplicitlyrequiredbythecustomerin...

Page 13: ...pump with the outlet valve closed for a period longer than 30 seconds If NO pressure or LOW pressure STOP the pump Refer to faultfinding chart for fault diagnosis The pump should run smoothly and wit...

Page 14: ...ne can present a danger to operators they must be shiel ded to avoid accidental contact If a 100 pro tection is not possible the machine access must be confined to the maintenance staff only If the te...

Page 15: ...gauge is directly proportional to SG Power absorbed is also directly proportional to SG It is therefore important to check that any change in SG will not overload the pump driver or over pressurize t...

Page 16: ...rking on the pump take measures to prevent an uncontrolled start Put a warning board on the starting device with the words Machine under repair do not start With electric drive equipment lock the main...

Page 17: ...maintenance If after some time the leakage becomes too great the glandshouldbe tightened againin order to return these to a normal level If re tightening is not possible new packing must be installed...

Page 18: ...allic surfaces if necessary with preservative is recommended at 6 monthly intervals 6 4 Recommended spares and consumable items 1500 2250 3011 3012 4130 4610 Dimensions in millimeters Gland packing Pu...

Page 19: ...fer to sectional dra wings for part numbers and identifica tion CAUTION Trouble Possible Causes Solutions Insuffcient flowrate Pump or suction pipe not completely filled Check and complete filling Air...

Page 20: ...bubbles in pipes Check and desecrate the pipes Suction level too low Check the available NPSH the required NPSH Reduce geometrical suction lift Reduce head losses in pipes and in fit tings diameter in...

Page 21: ...ressure Rotation speed too low check the dri ver Check the connection in the terminal box according to the voltage Presence of air Check and de aerate Suction pressure insufficient Check the available...

Page 22: ...English Installation and maintenance instructions Wilo Horizontal pumps NPG 8 Parts list and drawings 8 1 Sectional drawings Pump NPG Bearing Size 32 42 Pump NPG Bearing Size 55...

Page 23: ...English 26 Wilo AG 09 2005 Bearing 55a and 55b Pump NPG Bearing Size 70...

Page 24: ...stem etc are provided as separate documents in their original format If further copies of these are required they should be obtained from the sup plier for retention with these User Instructions Parts...

Page 25: ...ique directive Niederspannungsrichtlinie 2006 95 EG Low voltage directive Directive basse tension und entsprechender nationaler Gesetzgebung and with the relevant national legislation et aux l gislati...

Page 26: ...EG EG EMV Elektromagnetisk kompatibilitet 2004 108 EG EG Lavspenningsdirektiv 2006 95 EG Anvendte harmoniserte standarder s rlig 1 FIN CE standardinmukaisuusseloste Ilmoitamme t ten ett t m laite vas...

Page 27: ...lint Budapest T 36 23 889500 wilo wilo hu Ireland WILO Engineering Ltd Limerick T 353 61 227566 sales wilo ie Italy WILO Italia s r l 20068 Peschiera Borromeo Milano T 39 25538351 wilo italia wilo it...

Page 28: ...00 T 01805 W I L O K D 9 4 5 6 5 3 F 0231 4102 7126 Erreichbar Mo Fr von 7 17 Uhr Wochenende und feiertags 9 14 Uhr elektronische Bereitschaft mit R ckruf Garantie Kundendienst Anforderung Werksrepara...

Reviews: