9
ENGLISH
Technical modifications reserved !
Chart I: Functions of potentiometers and hook switches
(Fig. 2/3)
Switch/Pot.
Functions
Potentiometer for FLC-settings:
P1 for No. 1 pump
P2 for No. 2 pump
P3 for No. 4 pump
P4 for No. 3 pump
P8 to set pump stop time delay (0 – 2 min)
P9 to set pump stop time delay on low water cut-out (0 – 2 min)
Setting pressure setpoints (see pump duty chart, Fig. 5)
p
max2
P5 – base-load pump switch-off pressure
p
max1
P6 – base-load pump switch-off pressure
p
min
P7 – switch-on pressure for all pumps
S 1
Effect reversal for input low-water cut-out:
S 1 open: Plant runs on closed contacts on terminals WM,
plant stops on open contacts on terminals WM
S 1 closed: Reverse action.
S 2
Test run:
S 2 open: Test run activated
S 2 closed: Test run deactivated
S 5
Sensor input:
S 5 open: Plant stops on opening of sensor contacts (without fault signal)
S 5 closed: Plant runs on opening of sensor contacts (oll pumps)
S 3, 4, 7
Setting to the number of controlled pumps:
No. of pumps:
Hook switch positions:
S 3
S 4
S 7
1:
1
0
0
2:
0
1
0
3:
0
0
1
4:
0
0
0
0
open, 1
closed
Motor fuses, 6.3 diam. x 32 mm, 16 amps inert, 440 V
for pumps:
Phases:
L
0
1
L
0
2
L
0
3
F1-3
P1
Fuses:
F
0
1
F
0
2
F
0
3
F4-6
P2
F
0
4
F
0
5
F
0
6
F11-13
P3
F11
F12
F13
F14-16
P4
F14
F15
F16
F7
Control circuit fuse: 6,3 diam. x 32 mm, 0.1 mA, 250 V
Chart II: Settings of hook switches and potentiometers for different applications
Switch/Pot.
Pressure boosting
Fire services
S 5
*
0*
*
1*
S 2
0
0
S 1
0
0
Set FLC value to motor name plates
2
2
0.5
0.5
* 0
open, 1
closed