PLB-098
Oil Furnaces
–
Furnace Manual
18
11/13
5. DIMENSIONS AND RATINGS (continued)
Table 12: Airflow Data, Models with 1/3 HP PSC motors
0.2" (W.C.)
0.3" (W.C.)
0.4" (W.C.)
0.5" (W.C.)
0.6" (W.C.)
0.7" (W.C.)
HIGH
1420
1335
1240
1180
1085
1025
MED-HIGH
1275
1230
1170
1095
1045
960
MED-LOW
1015
1000
955
915
860
785
LOW
815
785
775
730
690
635
BLOWER
SPEED
EXTERNAL STATIC PRESSURE WITH AIR FILTER
Table 13: Airflow Data, Models with ½ HP ECM Motors
SW1- HEAT
DIP switch position
HEAT INPUT
(USGPH)
CFM with SW3-ADJ
DIP switch position A
CFM with SW3-ADJ
DIP switch position B
CFM with SW3-ADJ
DIP switch position C
A (1=OFF, 2=OFF)
0,70
1260
1385
1135
B (1=ON, 2=OFF)
0,55
1050
1155
945
C (1=OFF, 2=ON)*
0,55
850
935
765
D (1=ON, 2=ON)*
SW2- COOL
DIP switch position
A/C size
(TON)
CFM with SW3-ADJ
DIP switch position A
CFM with SW3-ADJ
DIP switch position B
CFM with SW3-ADJ
DIP switch position C
A (1=OFF, 2=OFF)
3,0
900
990
810
B (1=ON, 2=OFF)
2,5
750
830
675
C (1=OFF, 2=ON)
2,0
600
660
540
D (1=ON, 2=ON)
1,5
450
495
405
SW2- COOL
DIP switch position
A/C size
(TON)
CFM with SW3-ADJ
DIP switch position A
CFM with SW3-ADJ
DIP switch position B
CFM with SW3-ADJ
DIP switch position C
A (1=OFF, 2=OFF)
3,0
1200
1320
1080
B (1=ON, 2=OFF)
2,5
1000
1100
900
C (1=OFF, 2=ON)
2,0
800
880
720
D (1=ON, 2=ON)
1,5
600
660
540
SW4- DELAY
DIP switch position
HEAT INPUT
(USGPH)
PreRun On-Delay
CFM Level - Time
ShortRun On-Delay
CFM Level - Time
Off-Delay
CFM Level - Time
A (1=OFF, 2=OFF)
0,7
13% - 45 sec.
19% - 30 sec
38% - 3 min.
B (1=ON, 2=OFF)
0,55
13% - 45 sec.
19% - 60 sec
38% - 3 min.
*C (1=OFF, 2=ON)
0,55
13% - 60 sec.
13% - 60 sec
38% - 3 min.
D (1=ON, 2=ON)
All
13% - 30 sec.
100% - 0 sec
100% - 2 min.
No adjustment
required
A/C size
PreRun On-Delay
CFM Level - Time
ShortRun On-Delay
CFM Level - Time
Off-Delay
CFM Level - Time
-
All
NO DELAY
NO DELAY
100% - 90 sec
NOTE:
Disconnect main power to unit prior to changing DIP switch settings.
DELAY PROFILE FOR COOLING OR HEAT PUMP HEATING MODE
OIL HEATING MODE
24 VAC input (R) on W only
CONTINUOUS FAN
24 VAC input (R) on G only
COOLING OR HEAT PUMP HEATING MODE
24 VAC input (R) to G, Y/Y2 and O (for cooling)
In Cooling - Dehumidification mode, with no 24 VAC input to DH, the CFMs are reduced by 15%.
The CFMs shown are reduced by 20% if there is 24 VAC input to Y1 (first stage cooling mode)
Same value as DIP switch position A
* Alternate adjustement in oil-fired heating mode with higher temperature rise
DELAY PROFILE FOR OIL HEATING MODE
PreRun and ShortRun are the periods of time when the the blower starts at very low CFM to minimize the
distributon of cool air in the system and then runs up to normal speed.
Off Delay is the time required to cool down the heat exchanger with low CFMs, to minimize cool draft in the
air distribution system.