Williamson-Thermoflo PLB-098 LOW-BOY Instructions Manual Download Page 11

 

 

PLB-098 

Oil Furnaces

 – 

Furnace Manual

 

11/13  

11

 

1.12.

 

INSTALLATION OF ACCESSORIES 

Electrical shock hazard. 
Turn OFF electrical power at the fuse box or 
service panel before making any electrical 
connections and ensure a proper ground 
connection is made before connecting line 
voltage. 
Failure to do so can result in death or bodily 
injury. 

1.12.1.

 

Humidifier (HUM) 

The 120 VAC HUM terminals on the electronic board of the blower 
are tied directly to terminal 8 of the 9-terminal connector of the 
electronic board. It supplies 120 VAC electric powers when the 
burner is in operation. 
A 24 VAC signal can also be supplied from the W and C terminals 
on the blower electronic board to activate a switching relay. 
Also refer to the instructions supplied with the accessory. 

1.12.2.

 

Electronic Air Cleaner (EAC) 

The EAC terminal on the electronic board supplies 120 VAC when 
the blower is operating in the heating or air conditioning mode. This 
signal can be used to activate an electronic air cleaner that is not 
equipped with an air flow switch. If the cleaner is equipped with an 
air flow switch, the "S" terminal on the electronic board or one of the 
120 VAC terminals on the ECM electronic card can be used to 
provide a constant supply of 120 VAC. 
Also refer to the instructions supplied with the accessory. 

1.12.3.

 

Air Conditioner (or Heat Pump) 

An air conditioning coil may be installed on the supply air side 
ONLY. 

 

Poisonous carbon monoxide gas hazard. 
Install the evaporator coil on the supply side of the 
furnace ducting ONLY. 
An evaporator coil installed on the return air side 
of the ducting can cause condensation to form 
inside the heat exchanger, resulting in heat 
exchanger failure. This in turn, can result in death, 
bodily injury and/or property damage. 

A clearance of 15 cm (6") is required between the bottom of the coil 
drain pan and the top of the heat exchanger. If a heat pump is 
installed, a “dual-energy” thermostat, or other control is 
recommended, in order to prevent the simultaneous operation of the 
furnace and the heat pump. It also prevents a direct transition from 
heating by way of the heat pump to heating with oil. Refer to the 
thermostat instructions or those of another control used for the 
proper wiring. 

 

If a coil blower compartment is used, install air tight, motorized and 
automatic air dampers. Cold air coming from the coil and passing 
across the furnace can cause condensation and shorten the life of 
the heat exchanger. 

2.

 

OPERATION 

2.1.

 

START-UP 

Before starting up the unit, be sure to check that the following items 
are in compliance: 
1.  The electrical installation, the oil supply system, the venting 

system, combustion air supply and ventilation; 

2.  The blower access door is in place and the blower rail locking 

screws are well tightened; 

3.  The Blocked Vent Shut-Off (BVSO) is installed according to 

instructions (for chimney venting); 

4. 

The oil supply valve is open; 

5. 

The burner ‘’Reset’’ button is well pushed in or re-armed; 

6.  The preliminary air adjustments on the burner comply with the 

technical specifications in this manual; 

7.  The blower speed adjustments for heating and air conditioning 

are appropriate and according to the specifications in this 
manual; 

8. 

The blower start/stop delays are satisfactory; 

9.  The thermostat of the room is in the heating mode and is set 

higher than the ambient temperature. 

To start the unit, turn the main electrical switch on.  

2.2.

 

OPERATING SEQUENCE OIL HEATING 

MODE 

1. 

The W-R contact closes; 

2.  The burner motor starts up to pre-purge the combustion 

chamber for a period of 10 to 15 seconds. During that time a 
spark is established on the electrodes; 

3.  The solenoid valve opens and a flame is established. Shortly 

after, the electrodes cease to spark; 

4.  Then the blower runs up to full speed. The delay depends on 

the adjustments that were made on the electronic board, which 
controls the blower motor. Refer to Sections 1.10. to 1.11., as 
well as the CFM tables 12 and 13 for more details. 

5.  When the call for heat is satisfied, the solenoid valve closes, 

the flame goes out and the burner motor stops (after post purge 
delay, if applicable). 

6.  The blower stops shortly after the burner. The delay depends 

on the adjustments that were made on the electronic board that 
controls the blower. Refer to Sections 1.10. to 1.11., as well as 
the CFM tables 12 and 13 for more details. 

 

Note: A detailed operating sequence of the oil burner is 

outlined in the instructions provided with the burner. 

2.3.

 

CHECKS AND ADJUSTMENTS 

2.3.1.

 

Purging the oil line 

Open the bleed port screw and start the burner. Allow the oil to drain 
into a container for at least 10 seconds. The oil should flow 
absolutely free of white streaks or air bubbles to indicate that no air 
is being drawn into the suction side of the oil piping and pump. 
Slowly close and tighten the bleed screw. Once closed, the flame 
will light up. 

2.3.2.

 

Pressure adjustment 

The oil pressure must be adjusted according to the Table 11 of this 
manual. An adjustment screw and a connection for a pressure 
gauge are located on the oil pump for that purpose. Also refer to the 
burner instruction manual. 

2.3.3.

 

Combustion Check 

The heat exchanger metal surfaces may have oil 
and the baffle insulation also contains binders. 
These products will burn or evaporate when the 
unit operates for the first time. Because of that, 
the smoke reading may be skewed during the 
first minutes of operation. Therefore, the unit 
must operate during at least 60 minutes before 
taking any readings to adjust the combustion 
quality. Let the unit cool down before making any 
adjustments. 

 

The combustion check verification MUST be 
performed after the nozzle replacement or the 
burner cleaning. After these manipulations, the 
combustion parameters are necessarily modified. 
Refer also to the burner instruction manual. 

 

 

Summary of Contents for PLB-098 LOW-BOY

Page 1: ...y could result in severe personal injury death or substantial property damage When calling or writing about the furnace Please indicate furnace model number and serial number from rating label You may...

Page 2: ...bows 20 Always connect and seal a return air duct to the furnace unless the furnace is located in a large space such as an unpartitioned basement Route the return air duct to an adjacent room if no re...

Page 3: ...to a hazardous electrical condition and to premature failure of the equipment The minimum clearances from combustible material for each of the positions are specified in Table 1 If the furnace is inst...

Page 4: ...to the burner manufacturer s instructions Also the burner must be installed always in the same way independently of the furnace orientation 1 Position the mounting gasket between the mounting flange a...

Page 5: ...re the draft is either high or variable due to external conditions Follow the instructions provided with the regulator 1 5 4 Side wall Venting The heating unit is approved for side wall venting This s...

Page 6: ...xposure to the following substances a Permanent wave chemicals for hair b Chlorinated waxes and cleaners c Chlorine based swimming pool chemicals d Water softening chemicals e De icing salts or chemic...

Page 7: ...furnace installed with a 4 tons air conditioning evaporator coil Heating mode airflow is still 1050 CFM Cooling mode air flow use Equation 3 4 CFM 4 x 400 1600 CFM The larger number is 1600 CFM cooli...

Page 8: ...7 6 6 900 14 58 41 31 25 21 19 17 14 12 11 10 9 8 8 7 7 7 1000 16 64 45 34 28 23 20 18 15 13 11 10 9 9 8 8 7 7 1100 16 72 49 38 30 25 22 19 16 14 12 11 10 9 9 8 8 7 1200 16 54 41 33 27 24 21 17 15 13...

Page 9: ...600 12 59 38 28 22 19 16 15 13 700 12 69 44 32 25 21 18 16 15 13 800 14 50 36 29 24 20 18 16 14 900 14 56 41 32 26 22 20 18 15 1000 16 63 45 35 29 24 22 19 17 15 1100 16 69 49 38 31 26 23 21 18 16 120...

Page 10: ...he position of the wires on the electronic board of the unit and consult the wiring diagrams If the heating and air conditioning speeds are the same the RED wire must be moved to UNUSED LEADS on the e...

Page 11: ...BVSO is installed according to instructions for chimney venting 4 The oil supply valve is open 5 The burner Reset button is well pushed in or re armed 6 The preliminary air adjustments on the burner...

Page 12: ...ise is lower or exceeds the temperature specified in Table 10 change to the next lower or higher blower speed tap until the temperature rise falls to the target If the excessive temperature rise canno...

Page 13: ...6 Re mount lock and fasten the control box with the 2 screws removed in step 4 7 Re attach the assembly cover with the screws removed in step 2 8 Re establish power to the unit 3 3 CLEANING OF THE BUR...

Page 14: ...rough furnace checked not to exceed 85 F and the blower speed adjusted if necessary 19 Was the thermostat heat anticipator set per wiring diagram 20 Was the burner started and tested per burner manual...

Page 15: ..._____________________________Date installed_____________________________ Installation instructions have been followed Checkout sequence has been performed Above information is certified to be correct...

Page 16: ...000 0 70 MED HIGH HIGH 1255 1180 77 000 65 000 0 55 98 000 81 000 0 70 Model Input BTU h Blower motor HP Blower motor Speed adjustment 3 0 1 2 HP ECM 1 3 HP 4 speeds PLB098 DD PLB098 VS 10 x 10 Outpu...

Page 17: ...h Firing rate USGPH AFUE Nozzle Delavan Pump pressure PSIG Burner tube insertion length Inch Combustion air adjustment Turbulator Damper 77 000 0 55 86 6 0 50 70A 150 0 2 0 98 000 0 70 85 2 0 60 70A...

Page 18: ...1 ON 2 ON 1 5 600 660 540 SW4 DELAY DIP switch position HEAT INPUT USGPH PreRun On Delay CFM Level Time ShortRun On Delay CFM Level Time Off Delay CFM Level Time A 1 OFF 2 OFF 0 7 13 45 sec 19 30 sec...

Page 19: ...PLB 098 Oil Furnaces Furnace Manual 11 13 19 5 DIMENSIONS AND RATINGS continued Figure 9 Wiring Diagram 4 Speed Motor PSC...

Page 20: ...PLB 098 Oil Furnaces Furnace Manual 20 11 13 5 DIMENSIONS AND RATINGS continued Figure 10 Wiring Diagram Variable Speed Motor ECM...

Page 21: ...PLB 098 Oil Furnaces Furnace Manual 11 13 21 6 COMPONENTS AND REPLACEMENT PARTS Figure 11 Parts List With 4 Speed motor PSC B50126A...

Page 22: ...B03549 ELECTRICAL BOX 29 R02R008 HIGH LIMIT CTL205 30F 7 in 30 B03550 ELECTRICAL BOX COVER Panel only 31 B03118 01 ELECTRICAL KIT BVSO EXT 32 B03596 BURNER WIRE CHANEL 33 Z06G001 BLOCKED VENT SHUT OF...

Page 23: ...PLB 098 Oil Furnaces Furnace Manual 11 13 23 6 COMPONENTS AND REPLACEMENT PARTS continued Figure 12 Parts List With variable speed motor ECM B50127A...

Page 24: ...AL BOX SPACER 28 B03534 ELECTRICAL BOX 29 R02R008 HIGH LIMIT CTL205 30F 7 in 30 B03550 ELECTRICAL BOX COVER Panel only 31 B03118 01 ELECTRICAL KIT BVSO EXT 32 B03596 BURNER WIRE CHANEL 33 Z06G001 BLOC...

Page 25: ...f the furnace oil burner should shut down on flame failure the burner primary control will lock out Ask your service technician to show you the correct procedure to reset the primary control button NE...

Page 26: ...PLB 098 Oil Furnaces Furnace Manual 26 X40205 Rev B 11 13...

Reviews: