Trouble Shooting:

 

 

A. Output device does not turn on when specified humidity is reached.

 

Firstly please understand that the controller 

turns off

 the load when the target humidity is 

reached

. It 

turns

 

on

 the load only when the specified temperature is then 

exceeded

. For example, if you set HC=C, Lb=40, 

Hb=45, then the load will be turned off once the humidity reaches 40. The load will be turned on only when 

the humidity is 

OVER

 45.   

Then,  check  if  a  PT  value  is  specified.  If  you’ve  specified  a  PT  value,  during  the  delay,  the  WORKING 

indicator on screen will flash. Your device will be turned on after the specified time delay.

 

B. The controller displays EEE while beeping.

 

Please  check  if  the  3.5mm  plug  of  the  sensor  probe  is  inserted  completely  into  the  jack  on  side  of  the 

controller. If plugged in correctly, the probe is most likely defective. Please email us at [email protected] 

for a free probe replacement.

 

C. The controller will not turn on or shut off automatically.

 

Make sure the input power cord is inserted securely into the power outlet.

 

D. The screen displays LLL.

 

This means the humidity is below the minimum value that this controller can measure.

 

E. The screen displays HHH.

 

This means the humidity is over the maximum value that this controller can measure.

 

F. It keeps beeping when the temperature reaches a certain level.

 

This is usually because the alarm has been set. You can set AH=100 and AL=-0 to disable the alarm function.   

G, Lower Bound (Lb) or Higher Bound (Hb) automatically change after setting.

 

Lb must be less than Hb. If while setting either Lb or Hb you inadvertently make Lb greater than Hb, the 

other setting will automatically adjust to make Lb less than Hb. This can be corrected by carefully setting 

the temperature range and never allowing Lb to be greater than Hb or allowing Hb to be less than Lb. 

To ensure Hb and Lb are specified correct value, check  it again after  you quit setting. Hold UP  button to 

check Hb value and hold DOWN button to check Lb value on screen. 

 

 
 

WARNING

 

 

※ 

Rated Current of this controller is 10A

 (1100W @110V, or 2200W @220V). Check amps and watts of 

your output device in order to reduce the risk of fire caused by overloading.   

※ 

Make sure the input power cord is inserted completely in the socket as incomplete contact between 

the pins and plug can result in fire.

 

Summary of Contents for WH1436H

Page 1: ...roller Manual NEW VERSION UPDATE The outlet has been updated from a universal outlet to a standard U S outlet The operation has been simplified for ease of use An expanded humidity control range has been implemented Emai bill 1226 163 com ...

Page 2: ...turn it on UP DOWN In setting process SET indicator is on press UP DOWN to select parameter or adjust value of a parameter Holding the button allows for rapid number adjustments Use UP DOWN to check the Hb and Lb value When it s not in setting process SET indicator is off hold UP to check Hb Higher bound of your desired humidity range hold DOWN to check Lb Lower bound of your desired humidity rang...

Page 3: ...ected humidity reaches 85 the controller turns off the humidifier NOTE The WH1436H can accurately controls turn on and turn off points However there might be overshooting It s not the WH1436H s fault You can consider changing the power of your humidifier to compensate for the overshooting effect Example 2 Control a dehumidifier Keep humidity between 35 and 38 Alarm sounds when the temperature exce...

Page 4: ...lowing Lb to be greater than Hb or allowing Hb to be less than Lb To ensure Hb and Lb are specified correct value check it again after you quit setting Hold UP button to check Hb value and hold DOWN button to check Lb value on screen Further explanation about Compressor Time Delay PT The time delay is a way of over riding the humidity sensor so that regardless of detected humidity the output devic...

Page 5: ...screen displays LLL This means the humidity is below the minimum value that this controller can measure E The screen displays HHH This means the humidity is over the maximum value that this controller can measure F It keeps beeping when the temperature reaches a certain level This is usually because the alarm has been set You can set AH 100 and AL 0 to disable the alarm function G Lower Bound Lb o...

Reviews: