6.

 

Menu Instruction

 

 

Code 

Default    Range 

Definition 

Explanation

 

HC

 

C or H 

Working mode 

H for humidification, C for dehumidification 

Lb**

 

80

 

0~100

 

Lower  bound  of  your  desired 

humidity range 

In humidification mode, Lb is turn-on degree. 

In dehumidification mode, Lb is turn-off degree. 

Hb**

 

85 

0~100

 

Higher  bound  of  your  desired 

humidity range 

In humidification mode, Hb is turn-off degree. 

In dehumidification mode, Hb is turn-on degree. 

CA 

-12~12 

Calibrate the reading

 

Optional

. If measured humidity is 3% higher than 

the real humidity, set CA=

-3

PT*** 

0~30 

Compressor Time Delay 

(unit: minute)

 

Optional

.  It  defines  the  time  interval  of  2 

compressor cycles(On-Off) 

AH 

100

 

0~100

 

High humidity alarm

 

Optional

. It will beep once humidity exceeds 

AH. 

Press any key to stop alarm. 

AL 

0

 

0~100

 

Low humidity alarm

 

Optional

. It will beep once humidity is below 

AL. 

 

Press any key to stop alarm. 

**

 Lb must be less than Hb. 

If while setting either Lb or Hb you inadvertently make Lb greater than  Hb, the other setting will automatically adjust to 

make Lb less than Hb. This can be corrected by carefully setting the  humidity range and never allowing Lb to be greater 

than Hb or allowing Hb to be less than Lb. To ensure Hb and Lb are specified correct value, check it again after you quit 

setting. Hold UP button to check Hb value and hold DOWN button to check Lb value on screen. 

***Further explanation about Compressor Time Delay (PT):

 

The time delay is a way of over-riding the humidity sensor so that regardless of detected humidity the output device will 

not  turn  on  unless  the  specified time  duration  has  elapsed.  Under  dehumidification  mode,  after  the  power  is  on,  if  the 

measured humidity is higher than 

Hb

, the device won’t start output device immediately, but waiting for a delay time. 

Delay 

time is calculated right after the moment that the output device stops.

 

When  the  time  interval  of  two  on-off  cycles  is  larger  than  the  preset  delay  time,  the  controller  will  turn  on  the  output 

device immediately. (For example, PT=2. It’s been 3 minutes when the  humidity reaches the turn-on temperature again. 

The output device starts immediately.)   

When the time interval between two on-off cycles is less than preset delay, the controller won’t turn on the output device 

until preset delay is satisfied. (For example, PT=5. Your  output device stopped 3 minutes ago. Although it’s now turn-on-

degree, you have to wait 2 more minutes before your output device starts again.)

 

 

 
 
 

 
 

Summary of Contents for WH1436H

Page 1: ...roller Manual NEW VERSION UPDATE The outlet has been updated from a universal outlet to a standard U S outlet The operation has been simplified for ease of use An expanded humidity control range has been implemented Emai bill 1226 163 com ...

Page 2: ...turn it on UP DOWN In setting process SET indicator is on press UP DOWN to select parameter or adjust value of a parameter Holding the button allows for rapid number adjustments Use UP DOWN to check the Hb and Lb value When it s not in setting process SET indicator is off hold UP to check Hb Higher bound of your desired humidity range hold DOWN to check Lb Lower bound of your desired humidity rang...

Page 3: ...ected humidity reaches 85 the controller turns off the humidifier NOTE The WH1436H can accurately controls turn on and turn off points However there might be overshooting It s not the WH1436H s fault You can consider changing the power of your humidifier to compensate for the overshooting effect Example 2 Control a dehumidifier Keep humidity between 35 and 38 Alarm sounds when the temperature exce...

Page 4: ...lowing Lb to be greater than Hb or allowing Hb to be less than Lb To ensure Hb and Lb are specified correct value check it again after you quit setting Hold UP button to check Hb value and hold DOWN button to check Lb value on screen Further explanation about Compressor Time Delay PT The time delay is a way of over riding the humidity sensor so that regardless of detected humidity the output devic...

Page 5: ...screen displays LLL This means the humidity is below the minimum value that this controller can measure E The screen displays HHH This means the humidity is over the maximum value that this controller can measure F It keeps beeping when the temperature reaches a certain level This is usually because the alarm has been set You can set AH 100 and AL 0 to disable the alarm function G Lower Bound Lb o...