User Manual 5.1-1 (2018-09) 4
Subject to change
Series FK92K
Enclosed
release element
Enclosed
release element
FK90K fire dampers
Release mechanisms and actuators
Option:
Electric spring return actuator
with 70°C release element; protection class IP54.
M220-9/H
230 V AC; 9,2 VA; I
max
≤
2 ms
= 0.27 A.
M24-9/H
24 V AC/DC; 6.1 VA / 3.5 W; I
max
≤
2 ms
= 3.5 A.
Runtime: Opening
≈
60 s, closing
≈
21 s.
CLOSED/OPEN position indicators via limit switch for
5 A at
≤
240 V AC.
Halogen-free connection cable; 0.9 m long;
2 x 0.75 mm² and 6 x 0.75 mm². The AMP connector
plugs are detachable.
Option:
with 95°C release element.
Thermal-mechanical release mechanism
- Standard -
with 70°C release element; protection class IP54.
Option:
with coated 70°C release element.
Option:
with coated 95°C release element.
Option:
with
limit switch
E
Changeover with gold-plated contacts for 5
A at
250
V
AC or 24
V
DC; protection class IP67;
1
m silicone free connection cable 3
x
0.34
mm².
One or two can be plugged in for the CLOSED and/or OPEN
position indicator instead of blind caps.
Option:
with
remote release
, mounted on thermal-mechani-
cal release mechanism.
⇒
see page 35
FK90K fire dampers, series FK92K, are fitted with maintenance-free thermal-mechanical release mechanisms or
with thermal-electrical release mechanisms on the spring return actuators.
Release
occurs at a nominal temperature
of
70°C
or
95°C
. Coated release elements provide increased corrosion protection.
Electric spring return actuators also close the fire dampers if the supply voltage is interrupted. They reopen the fire
dampers as soon as the voltage is present again.
Release mechanisms and operation units can be replaced on site!
Enclosed
release
element
can be replaced
from the front.
Blind cap
can
be replaced with
the
OPEN limit
switch
.
Manual release
“Red button”
Lever for opening
the
fire damper.
Inserted
limit
switch
CLOSED
.
Option:
Electric spring return actuator
- Standard -
with 70°C release element; protection class IP54.
M220-10/H
230 V AC; 6.5 VA / 3 W;
I
max ≤ 5 ms
= 4 A
M24-10/H
24 V AC/DC; 4 VA / 2.5 W; I
max ≤ 5 ms
= 8.3 A
Runtime: Opening < 60 s, closing ≈ 20 s
CLOSED/OPEN position indicators via limit switches for 0.5 A
at ≤ 250 V AC or for 1 mA up to 3 A at 5 up to 250 V DC.
Halogen-free connection cable; 1 m long; 2 x 0.75 mm² and
6 x 0.75 mm². The AMP connector plugs are detachable.
Option:
with 95°C release element.
Button for function check
Button for function check