User Manual 5.1-1 (2018-09) 38
Subject to change
Series FK92K
Actuators M220-10/H, M24-10/H
Control voltages
230 V AC or 24 V AC/DC
Cable 6 x 0.75 mm²
Cable 2 x 0.75 mm²
OPEN
CLOSED
Limit switches
on thermal-mechanical release mechanisms
The CLOSED limit switches are actuated when the fire damper is closed, and
the OPEN limit switches are actuated when the fire damper is open.
Control voltages
230 V AC or 24 V AC/DC
Cable 2 x 0.75 mm²
Cable 6 x 0.75 mm²
33
5
3
2
OPEN
OPEN
CLOSED
CLOSED
Actuators M220-9/H, M24-9/H
1 Thermostats, smoke detectors and
switches must only be installed if required.
On site delivery.
2 Thermal-electric release element 70°C
or 95°C inside the fire damper casing.
3 Temperature cut-off approx. 70°C
outside the fire damper casing.
4 Electric actuator with limit switches for
OPEN-CLOSED position indicator.
The illustration shows the
de-energised operating position
where the fire dampers are closed.
•
The switches on the connection cables
can be removed if they are not being
used.
•
Due to their in-built thermal release
elements, all actuators must be stored
at temperatures not exceeding 50°C!
5 Button for function check
6 Lifting solenoid
7 Magnetic clamp
The right to allow for delivery variations
from the versions shown remains reserved.
Remote release
W220, G24
Closed during current flow
WU220, GU24
Closed during power interruption
1
7
Control voltages 230 V AC or 24 V DC
white
green
brown
Limit switch not actuated
Limit switch actuated
white
green
brown
Connection cable colour coding
1
6
Connection box for fire dampers
with electric spring return actuators
M220-10/H, M24-10/H,
M220-9/H, M24-9/H
⇒
see pages 37 and 39
FK90K fire dampers
Electrical connections