15 -  TROUBLE SHOOTING 

IMPORTANT NOTE: operations involving replacement of essential components must be carried out at our workshop, especially 
for instruments with flameproof certificate; this is to guarantee the user the total and correct restoration of the product original 
characteristics. 
 

MALFUNCTION 

PROBABLE CAUSE 

REMEDY 

Set point shift 

  Deposits on thermowell or bulb 

  Filling fluid leakage

 

  Check and clean surfaces 

  Replace the instrument

 

Slow response 

  Deposits on thermowell or bulb

 

  Check and clean surfaces

 

No actuation 

  Loosened electrical joints 

  Interrupted or short-circuited electrical line 

  Microswitch contacts damaged 

  Filling fluid leakage

 

  Check all electrical joints 

  Check the conditions of the electrical line 

  Replace the instrument 

  Replace the instrument

 

Undue actuation 

  Accidental shocks 

  Interrupted or short-circuited electrical line

 

  Modify the mounting 

  Check the conditions of the electrical line

 

 

Fig. 9 – Bracket for wall mounting 

Fig. 10 - Bracket for 2 pipe” 

 

 

 

 

 

Fig. 11 - Surface or 2” pipe mounting 

Fig. 12 - Surface mounting with Junction Box 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

1) 

Temperature switch 

5)  Branch Connection Fittings 

9) 

Fitting 

13)  Conduit Seal 

2) 

Capillary 

6)  Process line 

10)  Swivel adapter or cable gland 

14)  Junction box 

3) 

Thermowell 

7)  Mounting bracket 

11)  Junction Box (see fig 12) 

 

4) 

Bulb 

8)  2” pipe / Surface 

12)  Stem (see fig 12) 

 

 
 

Summary of Contents for TXS Series

Page 1: ...eights are not binding unless released on certified drawings CAUTION Before installing using or carrying out maintenance on the instrument it is necessary to read and understand the indications given...

Page 2: ...vates one or two simultaneous release electric microswitches The microswitches are of the rapid release type with automatic rearm When the temperature moves away from the set values returning towards...

Page 3: ...strument closes the circuit when the set point is reached with temperature on fall closure on fall The temperature switch must be kept in the normal installation position i e with the temperature conn...

Page 4: ...ion and accidental bumps Fig 6 Temperature switch for ambient temperature measurement 9 5 ELECTRICAL CONNECTIONS It is recommended to carry out the electrical connections according to the applicable s...

Page 5: ...external condition of the enclosure In case of flameproof or intrinsic safety instruments inspections of the electrical installation are to be carried out also according to customer procedures and at...

Page 6: ...ened electrical joints Interrupted or short circuited electrical line Microswitch contacts damaged Filling fluid leakage Check all electrical joints Check the conditions of the electrical line Replace...

Page 7: ...allation Annex 1 Model code 1 MODEL CODE TX For further information see datasheet 1 1 Ignition protection mode S Weatherproof A Ex d 1 2 Enclosure code material 2 Aluminium 4 316 s s B Direct Mounting...

Reviews: