15 - TROUBLE SHOOTING
IMPORTANT NOTE: operations involving replacement of essential components must be carried out at our workshop, especially
for instruments with flameproof certificate; this is to guarantee the user the total and correct restoration of the product original
characteristics.
MALFUNCTION
PROBABLE CAUSE
REMEDY
Set point shift
Deposits on thermowell or bulb
Filling fluid leakage
Check and clean surfaces
Replace the instrument
Slow response
Deposits on thermowell or bulb
Check and clean surfaces
No actuation
Loosened electrical joints
Interrupted or short-circuited electrical line
Microswitch contacts damaged
Filling fluid leakage
Check all electrical joints
Check the conditions of the electrical line
Replace the instrument
Replace the instrument
Undue actuation
Accidental shocks
Interrupted or short-circuited electrical line
Modify the mounting
Check the conditions of the electrical line
Fig. 9 – Bracket for wall mounting
Fig. 10 - Bracket for 2 pipe”
Fig. 11 - Surface or 2” pipe mounting
Fig. 12 - Surface mounting with Junction Box
1)
Temperature switch
5) Branch Connection Fittings
9)
Fitting
13) Conduit Seal
2)
Capillary
6) Process line
10) Swivel adapter or cable gland
14) Junction box
3)
Thermowell
7) Mounting bracket
11) Junction Box (see fig 12)
4)
Bulb
8) 2” pipe / Surface
12) Stem (see fig 12)