1 -  GENERAL 

1.1  FOREWORD 

The  wrong  choice  of  a  models  or  a  version,  as  well  as  the 
incorrect installation, lead to malfunction and reduce instrument 
life.  Failure  to  follow  the  indications  given  in  this  manual  can 
cause damage to the instrument, the environment and persons. 

1.2  ALLOWED OVERRANGES 

Temperature exceeding the working range can be 

allowed only 

for testing proposal 

up to the proof temperature. 

Continuous

 

temperature exceeding the (adjustable) “RANGE* (see fig 1) can 
be applied to the instrument, provided they are clearly stated in 
the instrument features (see fig.1, “MAX TEMPERATURE”). 
The  current  and  voltage  values  stated  in  the  technical 
specifications and data plate must 

not

 be exceeded: transitory 

overranges can have a destructive effect on the switch. 

1.3  TEMPERATURES 

The  temperature  of  the  instrument  is  influenced  by  the 
environmental and process temperature. Special attention must 
be taken to avoid the exceeding of the limits specified in table 1 
and 2. 
For the instrument version TX**B* (stem for direct mounting) the 
following table is applicable  
Table 1 – Temperature conditions 

Temp. 
Classification 

Ambient 
temperature 
range (Tamb) 

Max 

working 

temperature 
(T max.) 

Max electrical 

rating 

 (resistive load) 

T6 

-50 … +60 °C 

Shall  not  exceed  the 
maximum 
temperature specified 
on  the  nameplate 
(see fig.1 item 5). 

5A@24V d.c.; 

5A@250V a.c. 

See nameplate of 

the instrument 

(electrical rating) 

T5 
T4 

-50 … +85 °C 

T3 
T2 
T1 

For  the  instrument  versions  TX**C*,  TX**Q*,  TX**R*  (stem  for 
remote  mounting)  and  TX**S*  (helical  bulb  for  ambient 
temperature) the following table is applicable 
Table 2 – Temperature conditions 

Temperature 

Classification 

Ambient 

temperature 

range 

(Tamb) 

Max electrical rating 

 (resistive load) 

T6 

-50..+60 °C 

5A@24V d.c.; 5A@250V a.c. 

See nameplate of the instrument 

(electrical rating) 

T5 
T4 

-50..+85 °C 

T3 
T2 
T1 

2 -  OPERATING PRINCIPLE 

The  operating  principle  is  based  on  a  pressure  measuring 
element, connected via a capillary tube to a bulb. This system is 
partially filled with a volatile liquid, the residual free volume being 
filled  by  its  saturated  vapour.  In  this  system  a  pressure  is 
generated which is a non-linear function of bulb temperature; this 
pressure  acts  on  a  stainless  steel  diaphragm  which  applies  a 
force  to  a  stiff  disc;  this  force  is  directly  proportional  to  the 
temperature  value  to  which  the  bulb  is  submitted  and  is 
contrasted by an compression spring charged by a suitable bush. 
When  the  force  balance  point  is  exceeded,  the  stiff  disc  shifts 
and,  by  means  of  a  rigid  rod, 

activates  one  or  two 

simultaneous 

release 

electric 

microswitches

The 

microswitches are of the rapid release type with automatic rearm. 
When  the  temperature  moves  away  from  the  set  values, 
returning towards the normal values, the switch is rearmed. 

3 -  MODEL CODE 

See Annex 1 

4 -  NAMEPLATE AND MARKINGS 

The instrument is fitted with a metal plate bearing all its functional 
characteristics  and  in  case  of  flameproof  or  intrinsic  safety 
execution,  also  the  markings  prescribed  by  standard  IEC/EN 
60079-0.  Fig.1  shows  the  plate  mounted  on  flameproof 
instruments.  

 

Fig. 1 - Flameproof instruments plate  

 

1  Notified body that issued the type certificate and number of said 

certificate. 

2  CE  marking  and  identification  number  of  the  notified  body 

responsible for production surveillance. 

3  Apparatus  classification  according  to  ATEX  2014/34/EU 

directive. 

4  Type of protection and ambient temperature limits of operation. 
5  Max working temperature 
The  following  table  gives  the  relationship  between  hazardous 
areas, ATEX Categories and Equipment Protection Level (EPL) 
listed on the flameproof instrument nameplate. 

Hazardous area 

Categories 

according to 

2014/34/EU 

Directive (ATEX) 

EPL 

Gas, vapours, 
fog 

Zone 0 

1G 

Ga 

Gas, vapours, 
fog 

Zone 1 

2G or 1G 

Gb or Ga 

Gas, vapours, 
fog 

Zone 2 

3G, 2G or 1G 

Gc, Gb or Ga 

Dust 

Zone 20 

1D 

Da 

Dust 

Zone 21 

2D or 1D 

Db or Da 

Dust 

Zone 22 

3D, 2D or 1D 

Dc, Db or Da 

5 -  SPECIAL CONDITIONS FOR SAFE USE (X) 

The instrument cannot be repaired (see also throubleshooting). 
Should the instrument be installed without a junction box require 
an electric connection suitable for the mode of protection chosen 
at the free end of the cable. 
Should the instrument be installed in mines (Group I) the elettrical 
connection  has  require  to  be  protected  by  chemical  agents. 
Therefore  a  mounting  with  cable  protected  by  tubing  is 
mandatory. 

6 -  SET POINT ADJUSTMENT  

The compression of the spring can be regulated by means of the 
bush (for adjustment) in such a way that the switch is released 
when the temperature reaches (either increasing or decreasing) 
the desired value (set point). The instrument is usually supplied 
with the switches set at 0°C or at the lowest setting range value 
if this is higher than 0°C

 (factory calibration)

.  

The instrument is supplied with  an adhesive label showing the 
set point calibration value. With 

factory

 

calibration

 the values 

are not indicated on the label as these are temporary and will be 
modified  with  the  definitive  values.  Prior  to  installation  the 
instrument 

must  be

 

calibrated

  and  the  definitive  calibration 

values written on the label. 
If the instrument has been ordered with a 

specific

 

calibration

, it 

is  a  good  rule  to  check  the  calibration  values  marked  on  the 
relevant adhesive label, prior to installation. 

Summary of Contents for TXS Series

Page 1: ...eights are not binding unless released on certified drawings CAUTION Before installing using or carrying out maintenance on the instrument it is necessary to read and understand the indications given...

Page 2: ...vates one or two simultaneous release electric microswitches The microswitches are of the rapid release type with automatic rearm When the temperature moves away from the set values returning towards...

Page 3: ...strument closes the circuit when the set point is reached with temperature on fall closure on fall The temperature switch must be kept in the normal installation position i e with the temperature conn...

Page 4: ...ion and accidental bumps Fig 6 Temperature switch for ambient temperature measurement 9 5 ELECTRICAL CONNECTIONS It is recommended to carry out the electrical connections according to the applicable s...

Page 5: ...external condition of the enclosure In case of flameproof or intrinsic safety instruments inspections of the electrical installation are to be carried out also according to customer procedures and at...

Page 6: ...ened electrical joints Interrupted or short circuited electrical line Microswitch contacts damaged Filling fluid leakage Check all electrical joints Check the conditions of the electrical line Replace...

Page 7: ...allation Annex 1 Model code 1 MODEL CODE TX For further information see datasheet 1 1 Ignition protection mode S Weatherproof A Ex d 1 2 Enclosure code material 2 Aluminium 4 316 s s B Direct Mounting...

Reviews: