WIKA operating instructions model TR57-M
Do not cause any uneven loading by hanging heavy items on or through
connection cables strained tightly. It must be ensured that the probe
pad is mounted with flat contact. Tighten the cap nuts of the two adapter
components with the maximum permissible torque, so that the silicon
lining is not deformed and the piping is not affected negatively. Take care
that the cap nuts are evenly tightened with respect to each other.
Ideal
mounting position, since no air bubbles, deposits and increased
warming of the pipes falsify the measuring results.
Risky
mounting position, since the increased heating of the pipe can
lead to a falsification of the measuring result.
Ideal
mounting position, so long as no air bubble formation occurs.
Risky
mounting position, since the increased heating of the pipe
and the connection flange can lead to a falsification of the measuring
result.
min.150
min.150
min.150
F
5. Commissioning, operation