5. Commissioning, operation
The power supply for the flow switch must be made via an energy-limited electric circuit in accordance with section 9.4
of UL/EN/IEC 61010-1 or an LPS to UL/EN/IEC 60950-1 or class 2 in accordance with UL1310/UL1585 (NEC or CEC).
The voltage supply must be suitable for operation above 2,000 m above sea level, should the flow switch be used at
this altitude.
Requirement for shielding and grounding
The flow switch must be grounded in accordance with the grounding concept of the plant.
The instrument must be grounded via the process connection.
Connecting the instrument
1. Assemble the mating connector.
→ see chapter “Pin assignment”
2
.
Establish the plug connection.
Pin assignment
Circular connector M12 x 1 (4-pin)
4
3
1
2
U+
1
U-
3
S+ / SP2
1)
2
SP1
4
1)
Depending on the configuration of the output signals
Legend:
U+
Positive power supply terminal
U-
Negative power supply terminal
SP1 Switching output 1
SP2 Switching output 2
S+
Analogue output
C
Communication with IO-Link
Circular connector M12 x 1 (5-pin)
U+
1
U-
3
S+
5
SP1 / C
4
SP2
2
Summary of Contents for FSD-4
Page 68: ...14399527 01 05 2021 EN DE FR ES 68 WIKA operating instructions flow switch model FSD 4...
Page 104: ...14399527 01 05 2021 EN DE FR ES 104 WIKA mode d emploi pour le capteur de d bit type FSD 4 FR...
Page 138: ...14399527 01 05 2021 EN DE FR ES 138 WIKA operating instructions flow switch model FSD 4...
Page 139: ...14399527 01 05 2021 EN DE FR ES 139 WIKA operating instructions flow switch model FSD 4...