WIKA operating instructions flow switch, model FSD-4
EN
WARNING!
Physical injuries and damage to property and the environment caused by hazardous media
Upon contact with hazardous media (e.g. oxygen, acetylene, flammable or toxic substances), harmful
media (e.g. corrosive, toxic, carcinogenic, radioactive), and also with refrigeration plants and compres-
sors, there is a danger of physical injuries and damage to property and the environment.
▶
Should a failure occur, aggressive media with extremely high temperature and under high pressure
or vacuum may be present at the instrument.
▶
For these media, in addition to all standard regulations, the appropriate existing codes or regulations
must also be followed.
▶
Wear the requisite protective equipment.
For contact details see chapter 1 “General information” or the back page of the operating instructions.
In the event of any faults, first check whether the flow switch is mounted correctly, mechanically and electrically.
If complaint is unjustified, the handling costs will be charged.
Fault
Possible cause
Measure
No output signal
Cable break
Check the continuity
No/wrong supply voltage
Rectify the supply voltage
No output signal/cable break
Mechanical load too high
Replace probe with a suitable design
No/wrong output signal
Wiring error
Observe the pin assignment
Wrong output signal
Process temperature out of measuring range;
sensor drift caused by overtemperature
Check temperature range
Sensor break/short-circuit
Send the instrument to the manufacturer
Sensor drift caused by chemical attack
Check media compatibility
Wrong output signal and too long
response time
Wrong mounting geometry, for example mounting
depth too small and heat dissipation too high
Move the temperature-sensitive area of the
sensor into the medium
Deposits on the sensor element
Remove deposit
Signal span too small
Supply voltage too high/low
Rectify the power supply
Signal span drops
Moisture has entered
Fit the cable correctly
6. Faults
Summary of Contents for FSD-4
Page 68: ...14399527 01 05 2021 EN DE FR ES 68 WIKA operating instructions flow switch model FSD 4...
Page 104: ...14399527 01 05 2021 EN DE FR ES 104 WIKA mode d emploi pour le capteur de d bit type FSD 4 FR...
Page 138: ...14399527 01 05 2021 EN DE FR ES 138 WIKA operating instructions flow switch model FSD 4...
Page 139: ...14399527 01 05 2021 EN DE FR ES 139 WIKA operating instructions flow switch model FSD 4...