6
Technical Data
Power circuit
Devices with Operating voltage AC/DC 24 V
min.
typ.
max.
Operating voltage range
AC/DC 20.4 V
AC/DC 24 V
AC/DC 26.4 V
Residual ripple DC
2.4 V
SS
Rated power DC
--
1.3 W
1.6 W
Rated power AC
--
1.8 W / 3.2 VA
2.2 W / 3.9 VA
AC
50 Hz
--
60 Hz
Switch ON peak current (A1)
--
--
1.7 A
Rated short-circuit current
--
1400 mA
--
Operate time / recovery time
--
2 s / 3 s
--
Protection for control circuit supply
PTC thermistor
galvanische Trennung Versorgungskreis-Steuerkreis
No
Devices with Operating voltage AC 115 -120 V / AC 230 V
Operating voltage range U
N
= AC 115 -120 V
AC 93.5 V
AC 115 -120 V
AC 132 V
Operating voltage range U
N
= AC 230 V
AC 195 V
AC 230 V
AC 253 V
Rated power
--
2.0 W / 2.3 VA
2.4 W / 2.8 VA
Rated frequency AC
50 Hz
--
60 Hz
Protection for control circuit supply
Short-circuit-proof transformer
Isolation supply circuit / control circuit
Yes
Control circuit
Conductor resistanc in Y1-Y2 / Y1-Y3 ( at U
N,
regardless of
supply voltage)
--
--
70
Ω
Rated output voltage to supply input Y2
--
DC 24 V
Open circuit voltrage
--
--
DC 40 V
Rated current / peak current (inputs Y2, Y3)
--
--
90 mA / 1500 mA
Release time t
R
(K1, K2)
--
60 ms
80 ms
Operate time t
A1
(device with operating voltage AC 115 -120 V
/ AC 230 V)
--
180 ms
300 ms
Operate time t
A1
(
device with operating voltage AC/DC 24 V)
--
40 ms
60 ms
Operate time t
A2
--
40 ms
60 ms
Minimum ON time t
M1
(Y2)
t
A1
--
--
Minimum ON time t
M2
(Y3)
t
A2
--
--
Recovery time t
W
--
--
200 ms
Ready time t
B
--
--
300 ms
Output circuit
Contact equipment
3 enabling current paths with positively driven contacts (NO), 1 signalling current path
(NC)
Rated switching voltage U
n
AC/DC 230 V
Max. continuous current I
n
per current path NO/NC
8 A / 5 A
Max. total current for all current paths for devices with
operating voltage AC/DC 24 V
12 A
Max. total current for all current paths for devices with
operating voltage AC 115 -120 V / AC 230 V
8 A
Utilization category according to EN 60947-5-1
AC-15: Ue AC 230 V, Ie 5 A
DC-13: Ue DC 24 V, Ie 5 A
Mechanical service life
10 x 10
6
switching operations
short-circuit protection, fuse
max. 8 A
General data
Clearance/creepage distance between circuits
to EN 60664-1
depending on device version, see Isolation supply circuit
Overvoltage category
III
Rated impulse withstand level
4 kV
Rated voltage
AC 300 V
Power-frequency test voltage
2 kV
Contamination level of device: inside / outside
2 / 3
Protection class to EN 60529 Housing / terminals
IP 40/IP 20
Ambient / storage temperature
-25 ... +55 / -25 ... +75 °C
Weight for devices with operating voltage AC/DC 24 V
0.20 kg
Weight for devices with operating voltage AC 115 -120 V / AC 230
V
0.25 kg
Terminals and connection
screw-type terminals
spring-type terminals
Single-core or finely stranded
1 x 0.2 - 2.5 mm² / 2 x 0.2 - 0.75 mm²
2 x 0.2 - 1.5 mm²
Stripping length
max. 8 mm
Finely stranded with wire-end ferrule to DIN 46228
1 x 0.25 - 2.5 mm² / 2 x 0.25 - 0.5 mm²
2 x 0.25 - 1.5 mm² (trapezoid crimping)
Max. tightening torque
0.5 to 0.6 Nm
---