Applications
© 2010 Wieland Electric GmbH | BA000256 | 12/2012 (Rev. I)
59
The safety light curtain LC1 monitors the access to the machine zone. The optical muting
sensors LM1 and LM2 are OR-linked with light curtain LC1 (muting function).
Both muting sensors are pulse controlled and must be active to carry out the muting
function (light curtain bypass).
The muting function requires that outputs Q1, Q2, Q4 have previously been switched
on. This means that the vision of LC1 has to be uninterrupted for power on.
Lamp L1 indicates the active muting state (static on). The expected Reset signal at S1 is
indicated by blinking of L1. L1 control complies with EN 60496-1.
Restart is possible after exiting the danger zone and pushing Reset button S3.
samos
module
K3
Type
SA-BM-S1
FUNCTION
3.1
Function group
AB
External circuitry category (EN ISO 13849-1)
up to
4
Cross-circuit monitoring
X
Synchronous time monitoring
--
Stop category (EN 60204-1)
0
OFF delay
Q4
0 s
Retriggering ON
--
AUTO-RESET after POWER ON
MANUAL RESET after POWER ON
X
AUTO-RESET
MANUAL RESET
X
Comment
Crossmonitoring by safety sensors
Application example
A267
Machine zone
protection with light
curtain
Muting function
Category 4
Stop category 0
+ Combination
of fl AND
operation
1* MUTING
the conditional OR-
combination is valid only if
the result of the Reset
function before was =1
(see pages 46/47).