SA-BM Base Module
© 2010 Wieland Electric GmbH | BA000256 | 12/2012 (Rev. I)
27
Reset and feedback – activation of control inputs
S1
and
S2
S1
S2
Without
FEEDBACK
With
FEEDBACK
Bridge or
feedback circuit
Q1/Q2
Without
FEEDBACK
With
FEEDBACK
Bridge or
feedback circuit
Q3
Manual reset
(restarting inhibit)
Automatic reset
without starting
inhibit
___________________________________________________________________________
Retrigger and feedback – activation of control input
S3
S3
Without
FEEDBACK
With
FEEDBACK
Bridge or
feedback circuit
Q1/Q2 resp. Q4
Retrigger OFF
Retrigger ON
In functions without cross-circuit monitoring (see “Function Blocks – Overview”, page 30)
dynamic signals on outputs
X1
and
X2
are generated only during the configuring phase after
power on.
During the configuration phase (after power on) of manual Reset (with Reset button)
the corresponding
S
output must be open or connected to a high-ohm output (e.g. a PLC).
High or low potential will result in incorrect configuration.
___________________________________________________________________________
In order to monitor external contactors (FEEDBACK) that may be connected to outputs
Q1
-
Q4
the NC contacts of the respective contactors or output expansions must be connected
in series with the associated control inputs (see the tables here and page 47).
Feedback
via S1, S2
Feedback
via
S3
NOTE
Feedback circuit
monitoring