5
Running in period
For storage reasons the pump motor has a protective film on the
motor contacts. This may produce a burning smell for a period of up
to 5 days after installation, this is normal.
Electrical
Power supply
220-240V at 50Hz, fused at 3 Amps, via a double pole fused switch
(not supplied) with a minimum 3mm contact separation in each
contact.
Power Consumption
150 Watts maximum.
Plumbing Connections
Inlet
2 x 15mm Push-fit manifold.
Outlet
1/2” BSP male.
Operating Parameters
Ambient water temperature
Maximum temperature
30°C
Hot water temperature
Maximum inlet temperature
80°C
BS 6700 recommends hot water storage temperature should not
exceed 65°C.
Hot water should be set in the range of 60 to 65°C to meet
requirements of the shower unit.
Operating pressure (static)
Minimum static pressure
0.0075 bar
or
75mm
head of water.
Maximum static pressure
1bar
or
10m
head of water.
Note!
If 10m head, 1 bar pressure is available the use of a suitable
mixer shower would be more appropriate and give similar
performance.