Checking Battery Bank Connections
Power flows between the WhisperGen and battery bank via two power cables connected to the
terminals of the battery bank. The WhisperGen also monitors the battery bank voltage, current,
and temperature via electrical wires connected to the battery bank. If an electrical fault or warning
occurs, these electrical connections may need to be checked – refer to the trouble shooting
section. In general, the battery bank connections should be checked every three months.
To check the battery bank connections:
1.
Access the battery bank managed by the WhisperGen, and ensure that the battery bank
connections, as shown below, are intact and clean.
2. Check that the circuit breaker is closed.
3. Replace the voltage fuse if it has blown.
4. Check that the electrical insulation of the wires/cables is intact.
5.
Remove the enclosure lid.
FUEL
OFF
ON
Current Shunt
Current Sensing
Wires
Power Cables
Voltage Fuse
White
No assigned colour
No assigned colour
Green
Black
Violet
Red
Circuit
Breaker
Voltage
Sensing
Wires
Temperature
Sensor
(Optional)
Battery Bank
WTL0032
R
Personal Power Station
Do not touch the surfaces that are labelled as hot.