4-4
COMPRESSOR
Refer to page 3-18 for the procedure for servic-
ing the compressor.
1.
Unplug air conditioner or disconnect power.
2.
Disconnect the three wires from the com-
pressor terminals.
3.
Set the ohmmeter to the R x 1 scale.
4.
Touch the ohmmeter test leads to the
following compressor terminals. The meter
should indicate (approximately) as shown:
Terminal
R
to
C
= 1.1
Ω
Terminal
S
to
C
= 2.8
Ω
R
(WH)
S
(BN)
C
(BK)
Compressor
Terminals
Electrical Shock Hazard
Disconnect power before servicing.
Replace all parts and panels before operating.
Failure to do so can result in death or electrical shock.