P84022 F
Sheet 2 of 6
Table 2A: Current Ratings (AMPS) for 24VDC Models
Rated Average Current
Voltage 2415W
2430W
2475W
24110W
MEAN RMS MEAN RMS MEAN RMS MEAN RMS
16.0VDC 0.072
0.090
0.125
0.143 0.215 0.257 0.276 0.327
24.0VDC 0.053
0.079
0.085
0.113 0.140 0.200 0.169 0.256
33.0VDC 0.045
0.072
0.069
0.103 0.114 0.174 0.138 0.228
16.0VRMS ----- 0.105 ----- 0.141 ----- 0.262 ----- 0.330
24.0VRMS ----- 0.076 ----- 0.121 ----- 0.211 ----- 0.262
33.0VRMS ----- 0.070 ----- 0.105 ----- 0.185 ----- 0.229
Rated Peak Current *
Voltage 2415W
2430W
2475W 24110W
16.0VDC 0.185
0.264
0.456 0.584
24.0VDC 0.190
0.269
0.470 0.586
33.0VDC 0.195
0.274
0.474 0.596
16.0VRMS 0.182
0.259
0.458
0.586
24.0VRMS 0.185
0.268
0.472
0.590
33.0VRMS 0.197
0.286
0.492
0.596
Rated Inrush Current **
Voltage 2415W
2430W
2475W 24110W
16.0VDC 0.110
0.110
0.110 0.110
24.0VDC 0.165
0.165
0.165 0.165
33.0VDC 0.230
0.230
0.230 0.230
16.0VRMS 0.155
0.155
0.155
0.155
24.0VRMS 0.235
0.235
0.235
0.235
33.0VRMS 0.325
0.325
0.325
0.325
Table 2B: Current Ratings (AMPS) for 12VDC Models
Rated Average Current
Voltage 1215W
MEAN
RMS
8.0VDC 0.220 0.246
12.0VDC 0.129 0.187
17.5VDC 0.099 0.163
8.0VRMS ----- 0.246
12.0VRMS ----- 0.198
17.5VRMS ----- 0.170
Rated Peak Current *
Voltage 1215W
8.0VDC 0.410
12.0VDC 0.426
17.5VDC 0.438
8.0VRMS 0.414
12.0VRMS 0.426
17.5VRMS 0.444
Rated Inrush Current **
Voltage 1215W
8.0VDC 0.081
12.0VDC 0.100
17.5VDC 0.145
8.0VRMS 0.098
12.0VRMS 0.140
17.5VRMS 0.190
* Rated average current is measured using mean value. ** The time duration for the peak current is 100 microseconds.
*** The time duration for the inrush current is 4 milliseconds.
WARNING: MAKE SURE THAT THE TOTAL AVERAGE CURRENT, TOTAL PEAK CURRENT AND TOTAL INRUSH CURRENT
REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO THE SYSTEM’S PRIMARY AND SECONDARY POWER SOURCES, NAC
CIRCUITS, SM, DSM SYNC MODULES OR PS-12/24-8 POWER SUPPLY DO NOT EXCEED THE POWER SOURCES’ RATED CAPACITY
OR THE CURRENT RATINGS OF ANY FUSES ON THE CIRCUITS TO WHICH THESE APPLIANCES ARE WIRED. OVERLOADING
POWER SOURCES OR EXCEEDING FUSE RATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS
DURING AN EMERGENCY, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR
OTHERS.