Wheelock RSS-1215W Installation Instructions Manual Download Page 5

P84022 F 

Sheet 5 of 6 

MOUNTING PROCEDURES: 

CAUTION

:  

Check that the installed product will have sufficient clearance and wiring room prior to installing backboxes and 

conduit, especially if sheathed multiconductor cable or 3/4" conduit fittings are used. 

 

  1.  RSS models have an integrated Strobe Mounting Plate (SMP). 
  2.  The Strobe Mounting Plate (SMP) must be oriented correctly when it is mounted to the backbox.  Turn the SMP so that the 

arrow above the words “Horizontal Strobe” points to the top side of the SMP. 

  3.  RSS models can be flush mounted to a standard single-gang backbox (Figure A), 4” or 100mm backbox (Figure B) or double-

gang backbox (Figure C).  RSS models can also be surface mounted to a 4” or 100mm backbox (Figure B), double-gang backbox 
(Figure C) or the SHBB (Figure D).  RSSP models can be flush mounted to a 4” backbox (Figure E) or surface mounted to a 
SBL-2 backbox (Figure F). 

  4.  Mount the SMP first to the backbox.  Next slide the Beauty Plate over the SMP until the 2 snaps of the Beauty Plate engage with 

the SMP. 

  5.  The Beauty Plate can be removed from the strobe assembly once engaged.  First, gently insert a screwdriver into one of the slots 

located on the top and bottom edges of the Beauty Plate.  Second, gently pull away from the wall with the inserted screwdriver to 
disengage the snap.  Third, repeat the first and second steps for the second slot.  Finally, gently lift the Beauty Plate away from 
the SMP. 

  6.  Mounting hardware for each mounting option is supplied. 
  7.  Conduit entrances to the backbox should be selected to provide sufficient wiring clearance for the installed product. 
  8.  When terminating field wires, do not use more lead length than required.  Excess lead length could result in insufficient wiring 

space for the signaling appliance. 

  9.  Use care and proper techniques to position the field wires in the backbox so that they use minimum space and produce minimum 

stress on the product.  This is especially important for stiff, heavy gauge wires and wires with thick insulation or sheathing. 

10.  Do not pass additional wires (used for other than the signaling appliance) through the backbox.  Such additional wires could 

result in insufficient wiring space for the signaling appliance.  

WARNING:  WHEN INSTALLING STROBES IN AN OPEN OFFICE OR OTHER AREAS CONTAINING PARTITIONS OR 

OTHER VIEWING OBSTRUCTIONS, SPECIAL ATTENTION SHOULD BE GIVEN TO THE LOCATION OF THE STROBES SO 
THAT THEIR OPERATING EFFECT CAN BE SEEN BY ALL INTENDED VIEWERS, WITH THE INTENSITY, NUMBER, AND 
TYPE OF STROBES BEING SUFFICIENT TO MAKE SURE THAT THE INTENDED VIEWER IS ALERTED BY PROPER 
ILLUMINATION, REGARDLESS OF THE VIEWER'S ORIENTATION.  FAILURE TO DO SO COULD RESULT IN PROPERTY 
DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. 

 

RSS/RSSP-24110 strobe models are Listed for use in sleeping or non-sleeping areas when installed in accordance with appropriate 
NFPA Standards and the Authority Having Jurisdiction. 

WARNING:  INSTALLATION OF WHEELOCK 110 CANDELA STROBE PRODUCTS IN SLEEPING AREAS SHOULD BE WALL 

MOUNTED AT LEAST 24" BELOW THE CEILING  AS FOLLOWS:  (1) THE ON-AXIS (DIRECTLY IN FRONT OF LENS) LIGHT 
OUTPUT SHOULD BE DIRECTED AT THE EYE-LIDS OF THE SLEEPING PERSON, E.G. PILLOW END OF BED, BED HEAD; (2) 
NO PART OF THE BED SHALL BE MORE THAN SIXTEEN (16) FEET FROM THE STROBE NOTIFICATION APPLIANCE.  
INSTALLERS MUST ADVISE OWNERS AND OPERATORS OF BUILDINGS WITH SLEEPING OCCUPANTS, E.G. HOTELS AND 
MOTELS, TO WARN GUESTS, RESIDENTS AND EMPLOYEES TO NOT MOVE THE BED LOCATION TO A POSITION 
VIOLATING POINTS (1) AND (2) ABOVE OR SERIOUS INJURY AND/OR LOSS OF LIFE MAY OCCUR DURING A FIRE 
EMERGENCY. 

WARNING:  A SMALL POSSIBILITY EXISTS THAT THE USE OF MULTIPLE STROBES WITHIN A PERSON'S FIELD OF 

VIEW, UNDER CERTAIN CIRCUMSTANCES, MIGHT INDUCE A PHOTO-SENSITIVE RESPONSE IN PERSONS WITH EPILEPSY.  
STROBE REFLECTIONS IN A GLASS OR MIRRORED SURFACE MIGHT ALSO INDUCE SUCH A RESPONSE.  TO MINIMIZE 
THIS POSSIBLE HAZARD, WHEELOCK STRONGLY RECOMMENDS THAT THE STROBES INSTALLED SHOULD NOT 
PRESENT A COMPOSITE FLASH RATE IN THE FIELD OF VIEW WHICH EXCEEDS FIVE (5) Hz AT THE OPERATING 
VOLTAGE OF THE STROBES.  WHEELOCK ALSO STRONGLY RECOMMENDS THAT THE INTENSITY AND COMPOSITE 
FLASH RATE OF INSTALLED STROBES COMPLY WITH LEVELS ESTABLISHED BY APPLICABLE LAWS, STANDARDS, 
REGULATIONS, CODES AND GUIDELINES. 

 

NOTE

:  

NFPA

 72/ANSI 117.1 conform to 

ADAAG

 Equivalent Facilitation Guidelines in using fewer, higher intensity strobes within 

the same protected area. 

CAUTION

:  

Check the installation instructions of the manufacturers of other equipment used in the system for any guidelines or 

restrictions on wiring and/or locating Notification Appliance Circuits (NAC) and notification appliances.  Some system 
communication circuits and/or audio circuits, for example, may require special precautions to assure immunity from electrical noise 
(e.g. audio crosstalk). 

 

ANY MATERIAL EXTRAPOLATED FROM THIS DOCUMENT OR FROM WHEELOCK MANUALS OR OTHER DOCUMENTS 
DESCRIBING THE PRODUCT FOR USE IN PROMOTIONAL OR ADVERTISING CLAIMS, OR FOR ANY OTHER USE, 
INCLUDING DESCRIPTION OF THE PRODUCT'S APPLICATION, OPERATION, INSTALLATION AND TESTING IS USED AT 
THE SOLE RISK OF THE USER AND WHEELOCK WILL NOT HAVE ANY LIABILITY FOR SUCH USE. 

 

Summary of Contents for RSS-1215W

Page 1: ...H ANY OF THE FOLLOWING INSTRUCTIONS CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION INSTALLATION AND OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND OR OTHERS SPECIFICATIONS Table 1 Ratings Per UL 1971 Model Regulated Voltage VDC VRMS Voltage Range Limit VDC VRMS Strobe Candela CD Mounting Options RSS ...

Page 2: ...odels Rated Average Current Voltage 1215W MEAN RMS 8 0VDC 0 220 0 246 12 0VDC 0 129 0 187 17 5VDC 0 099 0 163 8 0VRMS 0 246 12 0VRMS 0 198 17 5VRMS 0 170 Rated Peak Current Voltage 1215W 8 0VDC 0 410 12 0VDC 0 426 17 5VDC 0 438 8 0VRMS 0 414 12 0VRMS 0 426 17 5VRMS 0 444 Rated Inrush Current Voltage 1215W 8 0VDC 0 081 12 0VDC 0 100 17 5VDC 0 145 8 0VRMS 0 098 12 0VRMS 0 140 17 5VRMS 0 190 Rated av...

Page 3: ... Min Typ 15W UL Min Typ 30W UL Min Typ 75W UL Min Typ 110W 0 15 0 24 30 0 46 75 0 103 110 0 149 5 13 5 24 27 0 46 67 5 103 99 0 152 10 13 5 24 27 0 45 67 5 104 99 0 151 15 13 5 24 27 0 46 67 5 100 99 0 151 20 13 5 23 27 0 43 67 5 101 99 0 148 25 13 5 23 27 0 43 67 5 98 99 0 140 30 11 3 21 22 5 41 56 3 94 82 5 135 35 11 3 20 22 5 40 56 3 89 82 5 129 40 11 3 19 22 5 39 56 3 83 82 5 124 45 11 3 18 22...

Page 4: ...he backbox used with each mounting option If these limits are exceeded there may be insufficient space in the backbox to accommodate the field wires and stresses from the wires could damage the product Although the limits shown for each mounting option comply with the National Electrical Code NEC Wheelock recommends use of the largest backbox option shown and the use of approved stranded field wir...

Page 5: ...OBES BEING SUFFICIENT TO MAKE SURE THAT THE INTENDED VIEWER IS ALERTED BY PROPER ILLUMINATION REGARDLESS OF THE VIEWER S ORIENTATION FAILURE TO DO SO COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND OR OTHERS RSS RSSP 24110 strobe models are Listed for use in sleeping or non sleeping areas when installed in accordance with appropriate NFPA Standards and the Authority Having J...

Page 6: ...ATELY TERMINATE IN THE EVENT ANY PART NOT FURNISHED BY WHEELOCK IS INSTALLED IN THE PRODUCT THE FOREGOING LIMITED WARRANTY SPECIFICALLY EXCLUDES ANY SOFTWARE REQUIRED FOR THE OPERATION OF OR INCLUDED IN A PRODUCT WHEELOCK MAKES NO REPRESENTATION OR WARRANTY OF ANY OTHER KIND EXPRESS IMPLIED OR STATUTORY WHETHER AS TO MERCHANTABILITY FITNESS FOR A PARTICULAR PURPOSE OR ANY OTHER MATTER USERS ARE SO...