FPAC2 UPgrAde
InstallatIon and operatIon manual
3 INsTAllINg The New dd/CF
reVIsION 0501
step 5:
Check if the FF Host System has the
support files for the FPAC device revision 5
(DD 0501 or higher). Open DeltaV Explorer,
click on Library\Device Definitions\Fieldbus
Devices\Westlock\FPAC VALVE CONTROLLER,
and check if the latest DD (REV 5) is installed.
See Figure 6.
step 6:
If it is not listed, contact Westlock
to receive the latest DD/CF files (0501)
or download it directly from the Fieldbus
Foundation registered products website, link
below
[2]
. See Figure 7.
NOTe
2. This uRL is maintained by FieldComm
group - Fieldbus Foundation division. In
case the link is not valid anymore contact
Westlock or browse the FieldComm
group - Fieldbus Foundation web site
to find the FPAC registration web page
shown before.
FIguRE 6
FIguRE 7
http://www.fieldbus.org/index.php?option=com_
mtree&task=viewlink&link_id=1836&ffbstatus=
Registered&Itemid=324
step 7:
Install the new DD/CF 0501 into the
Fieldbus Host System following the system
instructions.