WHL-016 Rev. 4.14.16
35
Figure 23 - Indoor and Outdoor Combustion Air - Single Pipe
I. Condensate Removal System
NOTE:
Check with your local gas company to determine if
combustion condensate disposal is permitted in your area. In
the state of Massachusetts, condensate must be neutralized
before entering a drain.
This boiler is a high efficiency appliance, and therefore produces
condensate: a by-product of the combustion process. A
condensate collection system with an internal float switch
monitors condensate level to prevent it from backing up into the
combustion system. There is a flexible line that must be piped to
a drain or condensate pump.
Condensate from the boiler is slightly acidic with a pH of 3.2
- 4.5. To avoid long term damage to the drainage system and
to meet local code requirements, Westinghouse recommends
neutralizing condensate with a Condensate Neutralizer Kit (Part
# 7450P-212 for EL-80/110/150/220/299/301, Part # 7350P-611
for EL-399). The neutralizer kit connects to the drain system
and contains limestone chips that neutralize the pH level of the
condensate. The neutralizer kit should be checked annually and
the limestone chips replenished if necessary. When replacing
the limestone chips, take care to ensure chips are no smaller
than ½” to avoid blockage in condensate piping (refer to Figure
26 for piping of the condensate neutralizer.)
Figure 24 - Condensate Detail
Summary of Contents for WBC 399
Page 14: ...WHL 016 Rev 4 14 16 14 Figure 6 Boiler Dimensions NOTE All Dimensions Are Approximate 055 080 ...
Page 21: ...WHL 016 Rev 4 14 16 21 Figure 9 Piping Symbol Legend ...
Page 42: ...WHL 016 Rev 4 14 16 42 Figure 33 Internal Connection Diagram ...
Page 65: ...WHL 016 Rev 4 14 16 65 Figure 37 Combustion System Replacement Parts 55 110kBTU Models ...
Page 67: ...WHL 016 Rev 4 14 16 67 Figure 39 Combustion System Replacement Parts 155 399kBTU Models ...