LEONARDO PRO X 3000/48 Li
User Manual
EN
7
5. Connection diagram that provides for the connection of all loads on the inverter's AC-OUT output. In this case, even in
the event of a blackout, all the loads in the home will be powered, up to the system output power (3kVA).
ATTENTION: In the case of connection diagram 1, it is necessary to install a switching interlock, controlled by the AC-
IN grid voltage which, in the event of a blackout, connects the privileged users on the inverter's EPS-OUT output.
CURRENT SENSOR INSTALLATION (TA)
Install the current sensor supplied following the connection diagrams 1-2-3-4 respecting the direction of the arrow:
the
direction of the arrow in the diagram must be the same as the direction shown on the sensor.
Pic.4 Current sensor wiring
L
L
INVERTER AND LOADS SIDE
GRID SIDE