INSTRUCTIONS PERTAINING TO THE INSTALLER
15.5 SEPARATED HORIZONTAL FLUE TERMINALS INSTALLATION OPTIONS
15.6 SEPARATED VERTICAL FLUE TERMINALS INSTALLATION OPTIONS
IMPORTANT
-
Ensure a minimum downward slope of 1 cm
towards the outside per each metre of duct length.
In the event of installation of the condensate collection kit, the angle of drain duct must be directed toward the boiler.
NOTE:
For C52 types, terminals for combustion air suction and combustion product extraction must never be fitted on
opposite walls of the building.
The maximum length of the suction duct must be 10 metres.
If the flue duct exceeds 6 m, the condensate collection kit (supplied as an accessory) must be fitted close to the boiler.
L max = 10 m
CG_1644 / 0503_0911
L max =
10 m
(L1 + L2) max =
30 m
CG_1643 / 0503_2201
15.4 SPLIT FLUE OVERALL DIMENSIONS
0504_1806/CG_1794