User & Installer

  (en)

GENERAL PRECAUTIONS 

This  boiler  has  been  designed  to  heat  water  to  a  temperature  lower  than  boiling  point  at  atmospheric  pressure.  It  must  be 

connected to a central heating system and to a domestic hot water supply system according to its performance and power output. 

Before having the boiler installed by a qualified service engineer, make sure the following operations are performed:

  

• 

Make sure that the boiler is adjusted to use the type of gas delivered by the gas supply. To do this, check the markings on the 

packaging and the data label on the appliance. 

• 

Make sure that the flue terminal draft is appropriate, that the terminal is not obstructed and that no exhaust gases from other 

appliances are expelled through the same flue duct, unless the latter has been specially designed to collect exhaust gas from 

more than one appliance, in compliance with current laws and regulations.

• 

Make sure that, if the boiler is connected to existing flue ducts, these have been thoroughly cleaned as residual products of 

combustion may detach from the walls during operation and obstruct the flow of fumes.

• 

To ensure correct operation and maintain the warranty, observe the following precautions:

  

1.   DHW circuit

  

1.1

 If the water is harder than 20 °F (1 °F = 10 mg calcium carbonate per litre of water), install a polyphosphate dispenser or an 

equivalent treatment system, compliant with current regulations.

  

1.2

 Thoroughly flush the system after installation of the appliance and before use.

  

1.3

 The materials used for the DHW circuit comply with Directive 98/83/EC.

  

2.   Heating circuit

To prevent corrosion, it is recommended that the PH of the system water is kept between 6.5 and 8.5.

Check the system water hardness and volume, taking into account that the top ups during the life cycle of the boiler will be lower 

than the curve represented in 

"SECTION" E

, as well as the type of boiler itself (Pmax < 30kW or Pmax > 30kW).

Example: Boiler (Pmax < 30kW), water hardness 5°d, system volume (300l + 300l top-ups) = 600l ► no treatment required.

SYSTEM WATER HARDNESS LEGEND - 

"SECTION" E

V (litres)

System top ups

D (°d)

Water hardness in German degrees

 

 

2.1 New system:

 Before installing the boiler, the system must be cleaned and flushed to eliminate residual thread-cutting swarf, 

solder and any solvents, using suitable off-the-shelf non-acid and non-alkaline products that do not damage metal, plastic and 

rubber parts. To protect the system from scale, use inhibitors such as SENTINEL X100 and FERNOX protector for heating circuits. 

Use these products in strict compliance with the manufacturers' instructions. Do not use leak sealers such as FERNOX CENTRAL 

HEATING LEAK SEALER and SENTINEL as they can damage the components of the boiler.

  

 

2.2 Existing system:

  Before  installing  the  boiler,  drain  the  system  and  clean  it  to  remove  sludge  and  contaminants,  using 

suitable proprietary products. Recommended cleaning products are: SENTINEL X300 or X400 and FERNOX regenerator for 

heating circuits. Use these products in strict compliance with the manufacturers' instructions. Remember that the presence of 

foreign bodies in the heating system can adversely affect boiler operation (e.g. overheating and excessive noise of the heat 

exchanger). Do not use leak sealers such as FERNOX CENTRAL HEATING LEAK SEALER and SENTINEL as they can damage 

the components of the boiler.

3.   Combustion air

Combustion air shall not contain corrosive substances, particularly fluorine and chlorine based vapours that can be found for 

example in solvents, detergents, propellant gases, etc.

  

Initial lighting of the boiler must be carried out by an authorised Service Engineer who must first ensure that:

  

• 

The rated data correspond to the supply (electricity, water and gas) data.

• 

That the installation complies with current regulations.

• 

The appliance is correctly connected to the power supply and earthed.

Failure to observe the above will render the warranty null and void. The names of the Authorised Service Centres are 

indicated in the attached sheet. Prior to commissioning, remove the protective plastic coating from the boiler. Do not use 

any tools or abrasive detergents to do this as you may damage the painted surfaces.

Do not leave any packaging (plastic bags, polystyrene, etc.) within the reach of children as they are a potential source of danger.

 

  

ENERGY-SAVING TIPS

Adjustment in the heating mode

Adjust the boiler flow temperature depending on the kind of system. For systems with radiators, set a maximum heating water flow 

temperature of approximately 60°C, and increase this value if the required room temperature is not reached. For systems with 

radiant floor panels, do not exceed the temperature indicated by the system designer. Use the External Sensor and/or Control 

Panel to automatically adjust the flow temperature to atmospheric conditions or the indoor temperature. This ensures that no more 

heat than that effectively necessary is produced. Adjust the room temperature without overheating the rooms. Every extra degree 

centigrade means consuming approximately 6% more. Also room ambient temperature depending on how the rooms are used. 

For example, the bedroom or the least used rooms can be heated to a lower temperature. Use the programmable timer and set the 

night-time room temperature at approximately 5°C lower than that during the day. There is no appreciable saving to be achieved 

by setting it any lower. Only in case of a prolonged absence, such as a holiday, should the temperature setpoint be lowered. Do 

not cover radiators as this prevents the air from circulating correctly. Do not leave the windows partially open to ventilate the rooms 

but open them completely for a short period. 

 

Domestic hot water

Setting the domestic hot water at the required temperature without mixing it with cold water saves a lot of money. Additional 

heating wastes energy and creates additional scale.

 

Summary of Contents for Star Condens+

Page 1: ...en CONDENSING GAS WALL HUNG BOILERS Instructions manual for users and fitters hu MAGAS HOZAM FALI G ZKAZ N Felhaszn l i s szerel i k zik nyv el...

Page 2: ...7 8 ROUTINE MAINTENANCE INSTRUCTIONS 7 INSTRUCTIONS PRIOR TO INSTALLATION 8 9 INSTALLING THE BOILER 8 9 1 BOILER DIMENSIONS AND GAS WATER CONNECTIONS 9 10 INSTALLING THE DUCTS 9 10 1 CONCENTRIC DUCTS...

Page 3: ...Call an Authorised Service Centre SMELL OF COMBUSTION FUMES Switch off the boiler Open all the doors and windows to ventilate the room Call an Authorised Service Centre FLAMMABLE MATERIAL Do not use...

Page 4: ...udge and contaminants using suitable proprietary products Recommended cleaning products are SENTINEL X300 or X400 and FERNOX regenerator for heating circuits Use these products in strict compliance wi...

Page 5: ...ler information menu Fault in progress Set unit of measurement SI US 1 1 ADJUSTING THE CH AND DHW FLOW TEMPERATURE Press and respectively to adjust the CH and DHW flow temperature if an external stora...

Page 6: ...flow sensor faulty Call the Authorised Service Centre 28 NTC fumes sensor faulty Call the Authorised Service Centre 40 NTC return sensor faulty Call the Authorised Service Centre 50 NTC domestic hot...

Page 7: ...Off operating mode the boiler stays off but the electrical circuits remain powered and the anti freeze function remains active 7 FILLING THE SYSTEM To fill the system pull out the telescopic tap A at...

Page 8: ...f danger Initial lighting of the boiler must be carried out by an authorised Service Engineer as indicated on the attached sheet Failure to observe the above will render the guarantee null and void AD...

Page 9: ...lable accessories as described below The boiler has been designed for connection to a vertical or horizontal coaxial flue air duct The boiler can also be used with separate ducts using the accessory s...

Page 10: ...ower supply using the supplied three pin cable observing correct Live Neutral polarity Use a double pole switch with a contact separation of at least 3 mm When replacing the power supply cable fit a h...

Page 11: ...hydraulic connection of the external storage boiler is shown in annex SECTION F Connect the DHW priority sensor NTC to terminals 5 6 on terminal block M2 The sensitive element of the NTC sensor must b...

Page 12: ...ined from the primary circuit To enable the system gas extraction function press buttons together for 6 seconds When the function is active On appears on the display for a few seconds followed by prog...

Page 13: ...boiler to its ignition power Wait for the value of CO2 to stabilise and then adjust as described in point 4 of the procedure the power value is a number 100 and 0 then save point 5 press again to take...

Page 14: ...ol and PCB 02 the temperature request is the Remote Control setpoint The Room Thermostat enable the gas boiler operates 03 the calculated setpoint depends on the origin of the request PCB or Remote Co...

Page 15: ...W systems which when flow temperature falls below 5 C operates the burner until a flow temperature of 30 C is reached This function is enabled when the boiler is switched on the gas supply is open and...

Page 16: ...that it is properly connected 17 1HYDRAULIC UNIT For special areas where the water is harder than 20 F 1 F 10 mg calcium carbonate per litre of water install a polyphosphate dispenser or an equivalent...

Page 17: ...function is enabled and flash on the display After the ignition sequence which can also take place after a few attempts the boiler performs three operations each lasting approximately 1 minute going...

Page 18: ...ure in DHW circuit bar 0 15 0 15 0 15 Minimum flow of water in DHW circuit l min 2 0 2 0 2 0 Production of DHW with T 25 C l min 13 8 16 1 18 9 Production of DHW with T 35 C l min 9 8 11 5 13 5 Specif...

Page 19: ...consumption Full load elmax kW 0 030 0 030 0 030 0 040 0 040 Part load elmin kW 0 013 0 013 0 013 0 013 0 013 Standby mode PSB kW 0 003 0 003 0 003 0 003 0 003 Other items Standby heat loss Pstby kW...

Page 20: ...l space heating energy efficiency class A A A A A Water heating energy efficiency class A A A Rated heat output Prated or Psup kW 12 24 20 24 28 Space heating Annual energy consumption GJ 38 75 63 75...

Page 21: ...NFORM CI K MEN 26 6 A KAZ N KIKAPCSOL SA 26 7 BERENDEZ S FELT LT S 26 8 RENDES KARBANTART SI UTAS T SOK 26 A BESZEREL ST MEGEL Z EN RV NYES FIGYELMEZTET SEK 27 9 A KAZ N BESZEREL SE 27 9 1 A KAZ N M R...

Page 22: ...ablakot H vja a felhatalmazott M szaki Szervizk zpontot G S SZAG Kapcsolja ki a kaz nt Szell ztesse ki a helyis get az ablak s az ajt kinyit s val H vja a felhatalmazott M szaki Szervizk zpontot GY L...

Page 23: ...kell tiszt tani iszapt l s szennyez d sekt l a kereskedelemben kaphat erre alkalmas term kek haszn lat val A tiszt t shoz javasolt term kek az al bbiak SENTINEL X300 vagy X400 s FERNOX f t rendszer h...

Page 24: ...amoz s men Manu lisan helyre ll that rendelleness g gomb Kaz n inform ci k men Meghib sod s folyamatban Be ll tott m rt kegys gek SI US 1 1 A F T S S A HASZN LATI MELEGV Z ODAIR NY H M RS KET NEK SZAB...

Page 25: ...dott H vja a felhatalmazott m szaki szervizk zpontot 28 A f stg z h m rs klet t m r NTC h rz kel meghib sodott H vja a felhatalmazott m szaki szervizk zpontot 40 A visszat r v zh m rs kletet m r NTC r...

Page 26: ...KAPCSOL SA A kaz n kikapcsol s hoz a k tp lus kapcsol val meg kell szak tani a k sz l k elektromos energiaell t s t A V delem m k d si m dban a kaz n kikapcsol sra ker l de az elektromos k r k fesz lt...

Page 27: ...ol kell tartani mert lehets ges vesz lyforr st jelentenek Az els begy jt st a felhatalmazott m szaki szervizszolg latnak kell v geznie a mell kelt lap szerint A fentiek be nem tart sa eset n a garanci...

Page 28: ...Az oszt tartoz k seg ts g vel elk l n tett cs vezet kekkel is lehet haszn lni a kaz nt FIGYELMEZTET S C13 C33 Az osztott kivezet k v gelemeit egy 50 cm es oldal n gyzeten bel l kell elhelyezni A r sz...

Page 29: ...zis f ldel s t ph l zatra kell csatlakoztatni a vele adott h romeres vezet kkel a VONAL NULLA polarit st betartva A csatlakoztat st k tf zis kapcsol seg ts g vel kell elv gezni gy hogy az rintkez k le...

Page 30: ...z t rt n csatlakoztat sra A v zmeleg t hidraulikus csatlakoztat s t F SECTION mell klet br ja t nteti fel Csatlakoztassa az NTC els bbs gi haszn lati melegv z szond t az M2 kapocsl c 5 6kivezet seihe...

Page 31: ...a funkci bekapcsol a kijelz n n h ny m sodpercre megjelenik az On felirat melyet a 312 programsor k vet Az elektronikus alaplap 10 perces id tartamra aktiv lja a szivatty be kikapcsol si ciklust A fun...

Page 32: ...tsa V rja meg hogy a CO2 rt ke stabiliz l djon majd v gezze el a szab lyoz st az elj r s 4 pontj ban ismertetettek szerint a teljes tm ny rt ke egy 100 s 0 k z tti sz m majd mentse az rt ket 5 Pont ny...

Page 33: ...2 a h m rs klet a T vvez rl n be ll tott rt kkel egyezik meg A Helyis g Termoszt t enged lyezi letiltja a kaz n m k d s t 03 a sz m tott alap rt k az ig ny eredet t l f gg PCB vagy T vvez rl a PCB Hel...

Page 34: ...marad ameddig a v zh m rs klet el nem ri a 30 C ot Ez a funkci akkor m k dik ha a kaz nt ram al helyezt k van g z s a rendszer nyom sa megfelel az el rt rt knek Szivatty tmozgat s Ha 24 r n t nincs h...

Page 35: ...a v z kem nys ge nagyobb mint 20 F 1 F 10 mg kalcium karbon t liter v z egy polifoszf t adagol vagy egy a hat lyos szabv nyoknak megfelel ezzel egyen rt k rendszer beszerel s t javasoljuk MAGYAR ZAT...

Page 36: ...b lkoz st is ig nyelhet bekapcsol si sorrend ut n a kaz n h rom m veletet eszk z l mindegyik kb 1 perc id tartam el bb a maxim lis teljes tm nyen majd a bekapcsol si teljes tm nyen v g l pedig a mini...

Page 37: ...r 0 15 0 15 0 15 A legalacsonyabb el rhet HMV t rfogat ram l perc 2 0 2 0 2 0 Haszn lati melegv z el ll t s T 25 C eset n l perc 13 8 16 1 18 9 Haszn lati melegv z el ll t s T 35 C eset n l perc 9 8 1...

Page 38: ...gyaszt s Teljes terhel s elmax kW 0 030 0 030 0 030 0 040 0 040 R szterhel s elmin kW 0 013 0 013 0 013 0 013 0 013 K szenl ti zemm d PSB kW 0 003 0 003 0 003 0 003 0 003 Egy b elemek K szenl ti h ves...

Page 39: ...is helyis gf t si energiahat konys gi oszt ly A A A A A V zmeleg t si energiahat konys gi oszt ly A A A N vleges h teljes tm ny Prated vagy Psup kW 12 24 20 24 28 Helyis gf t s ves energiafogyaszt s G...

Page 40: ...43 2 44 3 44 4 44 5 45 6 45 7 45 8 45 46 9 46 9 1 47 10 47 10 1 47 10 2 48 11 48 11 1 49 11 2 49 12 50 12 1 50 12 2 50 12 3 50 12 4 CO2 50 CO2 51 13 51 14 51 15 53 16 53 EE 2016 426 92 42 2014 30 E 20...

Page 41: ...41 e l 7729500 03 12 19 17 54 17 1 54 17 2 54 17 3 54 17 4 55 17 5 55 55 18 55 19 56 20 57 21 58...

Page 42: ...98 83 2 pH 6 5 8 5 SECTION E Pmax 30kW Pmax 30kW Pmax 30kW 5 d 300l 300l 600l SECTION E V D d 2 1 SENTINEL 100 FERNOX FERNOX CENTRAL HEATING LEAK SEALER SENTINEL 2 2 Y SENTINEL X300 X400 FERNOX FERNO...

Page 43: ...43 e l 7729500 03 12 19 1 6 1 2 Reset SI US 1 1 C 20 C 10 2 1 C 1 2 3...

Page 44: ...7729500 03 12 19 44 e l 2 5 C 30 C 3 4 RESET RESE 2 09 10 12 13 15 18 19 2 20 NTC 28 NTC 40 NTC 50 NTC 53 55 83 87 92 109 110 2 117 2 7 bar 118 125 2 128 2 129 130 NTC 2 133 5 2 134 2 135 2 154 160...

Page 45: ...7729500 03 12 19 178 270 317 162 321 163 NTC 384 164 2 385 165 175V 431 5 15 5 1 00 06 C 01 C 07 C 02 C 08 C 03 09 13 04 14 Open Therm 05 bar 15 18 6 7 A 1 1 5 bar B B 1 1 5 bar A C A B C WESTEN 8 77...

Page 46: ...7729500 03 12 19 46 e l 0 C 16 60 C 9 STAR CONDENS 33 4 7 8 1 1 2 3 4 7223491a 9 7 8 5 6 7223491b...

Page 47: ...47 e l 7729500 03 12 19 SECTION C G3 4 30 m 9 1 A D B E C G1 2 G3 4 F SECTION C 10 C13 C33 50 cm C53 C63 100 Pa 100 C EN 1856 1 C43 C83 1 10 1 LAS 90 360 45 18 mm 90 1 45 0 5 90 5 cm SECTION D...

Page 48: ...0 2 80 B A 90 45 90 0 5 45 0 25 90 C 360 100 60 mm 80 mm SECTION D 11 230 V 3 mm HAR H05 VV F 3x0 75 mm2 8 mm 2 SECTION B 2A M1 230 V M1 L N M1 L N 1 2 1 2 M1 M2 1 2 3 4 1 12 1 24 4 5 24 28 33 5 6 1 1...

Page 49: ...0 V L N M1 1 2 11 2 11 2 1 3 4 1 12 1 24 4 5 24 28 33 Kt Kt SECTION E 00 90 SECTION E 11 2 2 1 12 1 24 SECTION F C 5 6 M2 C 35 C 60 C P03 05 14 8 9 10 M2 11 2 3 SECTION G Z 1 n EV R RT 1 1 3 1 2 M1 P0...

Page 50: ...7729500 03 12 19 50 e l 12 12 1 000 6 On 2 312 10 2 6 E118 12 2 6 On 312 10 6 12 3 6 On 303 1 6 15 12 4 CO2 CO2 O2 CO2 O2 G20 CO2 O2 CO2 O2 9 0 4 8 8 7 5 4 8 3 9 7 6 1 3 6 8 4 9 0 5 9 4 8 CO 1000 ppm...

Page 51: ...51 e l 7729500 03 12 19 CO2 CO2 6 On 304 100 100 CO2 00 304 CO2 3 3 1 100 CO2 5 5 CO2 4 100 0 5 CO2 4 00 6 1 13 Pi 14 6 P01 16 01 Pi...

Page 52: ...P09 P10 setpoint Open Therm 230V 00 setpoint 01 setpoint PCB 02 setpoint 03 setpoint PCB a PCB setpoint b setpoint ULt c PCB setpoint 00 P11 P12 P13 0 100 100 100 82 82 84 P14 0 100 100 P15 0 100 00...

Page 53: ...53 e l 7729500 03 12 19 15 NTC 0 5 bar 3 5 C 30 C 24 10 24 3 bar 16 SECTION E SECTION E Q H MIN MAX...

Page 54: ...7729500 03 12 19 54 e l 17 4 17 1 20 F 1 F 10 mg SECTION F 17 2 E SECTION F 1 E 2 E NTC D OR Molykote 111 17 3 SECTION F Cillit FFW AL Beckinser HF AL...

Page 55: ...55 e l 7729500 03 12 19 17 4 SECTION F 17 5 CO2 CO2 6 On 3 303 3 1 ESC 18 90...

Page 56: ...bar 0 8 bar 8 0 8 0 8 0 bar 0 15 0 15 0 15 l min 2 0 2 0 2 0 T 25 C l min 13 8 16 1 18 9 T 35 C l min 9 8 11 5 13 5 D EN 13203 1 l min 11 5 13 4 15 8 C 25 80 25 80 25 80 25 80 25 80 C 35 60 35 60 35 6...

Page 57: ...97 5 97 5 97 7 elmax kW 0 030 0 030 0 030 0 040 0 040 elmin kW 0 013 0 013 0 013 0 013 0 013 PSB kW 0 003 0 003 0 003 0 003 0 003 Pstby kW 0 075 0 075 0 075 0 075 0 075 Pign kW 0 000 0 000 0 000 0 00...

Page 58: ...3 12 19 58 e l 21 WESTEN STAR CONDENS 1 12 1 24 24 28 33 XL XL XXL A A A A A A A A Prated Psup kW 12 24 20 24 28 GJ 38 75 63 75 87 kWh 1 42 42 79 GJ 2 18 18 22 92 92 92 92 93 83 83 86 LWA dB 51 50 49...

Page 59: ...59 e l 7729500 03 12 19...

Page 60: ...7729500 03 12 19 60 S E C T I O N A 7729514...

Page 61: ...Haszn lati melegv z h cser l 14 Gas valve G zszelep 15 NTC heating sensor flow return F t si NTC szonda NTC 16 Venturi Leveg g z Venturi cs vek Venturi 17 Fan Ventil tor 18 Air gas blend manifold Lev...

Page 62: ...X13 X5 X35 X37 X36 X15 L N X20 X10 X3 X1 L N G V G V G V G V G V G V G V R R R C C V R N C C R B C V N R C C C R B C C G V G V M C M C C N M C M G V G V G V G V M1 1 2 3 4 6 5 7 8 9 10 11 15 16 17 10...

Page 63: ...re sensor Nyom s rz kel 10 Heating return sensor A f t si visszat r g h rz kel je 11 Heating flow sensor A f t si el remen g h rz kel je 12 NTC DHW sensor A haszn lati melegv z NTC t pus h rz kel je N...

Page 64: ...X34 X13 X5 X35 X37 X36 X15 L N X20 X10 X3 X1 L N G V G V G V G V G V G V G V R R R C C V R N C C V N R C C C C G V G V M C M C C N M C M G V G V G V G V M1 1 2 3 4 6 5 7 8 10 15 16 10 2 3 4 5 6 7 8 9...

Page 65: ...eating return sensor A f t si visszat r g h rz kel je 10 Heating flow sensor A f t si el remen g h rz kel je 11 Accessories connection Tartoz kok csatlakoztat sa 12 Outdoor sensor K ls h rz kel 13 Boi...

Page 66: ...7729500 03 12 19 66 S E C T I O N C 7218789 01 53 5 41 5...

Page 67: ...67 S E C T I O N C 7729500 03 12 19 53 5 41 5 A 168 5 53 5 41 5 A 168 5 130 22 22...

Page 68: ...7729500 03 12 19 68 S E C T I O N D 25 mm...

Page 69: ...D Lmax 9 m 60 100 mm Lmax 24 m 80 125 mm E Lmax 10 m 60 100 mm Lmax 25 m 80 125 mm F G Lmax 10 m 60 100 mm Lmax 25 m 80 125 mm H Lmax 8 m 60 100 mm Lmax 23 m 80 125 mm I Lmax 9 m 60 100 mm Lmax 24 m 8...

Page 70: ...9 70 S E C T I O N E 0 0 5 1 1 5 2 2 5 3 3 5 4 4 5 5 5 5 6 0 200 400 600 800 1000 1200 H mH2O Q l h Min Max 0 100 200 300 400 500 600 700 800 900 1000 0 5 10 15 20 25 30 35 40 45 V l D d Pmax 30 kW Pm...

Page 71: ...71 S E C T I O N F 7729500 03 12 19...

Page 72: ...7729500 03 12 19 72 S E C T I O N F 7715701 4 5 1 CG_2522...

Page 73: ...73 S E C T I O N G 7729500 03 12 19...

Page 74: ...DOS MEGV LTOZTATOTT PARAM TEREK ZM N N PARAMETRY ZMENEN PARAMETRE PARAM TRES MODIFI S GEWIJZIGDE PARAMETERS MODIFIZIERTE PARAMETER PARAMETRI MODIFICA I N Sz Nr VALORE VALUE VALOR VALORES RT K HODNOTA...

Page 75: ...75 7729500 03 12 19...

Page 76: ...7729500 03 12 19 36061 Bassano del Grappa VI ITALIA Via Trozzetti 20 Servizio clienti tel 0424 517800 Telefax 0424 38089 www westen it...

Reviews: